| 2004-05-06 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 03060499 |
| | ADD: 4017 PINEWOOD AVE |
| | CONT: PLAN REVIEW-TBA |
| | CONTACT: JEFF HALVERSON |
| | TEL: (561)659-8040 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1) THE DRAWINGS ARE "RED LINED" BUT THE |
| | DESIGN PROFESSIONAL WHO DESIGNED THE |
| | PROJECT NEVER "SIGNED AND DATED" THE RED |
| | LINED CHANGES. PLEASE HAVE THE DESIGN |
| | PROFESSIONAL WHO DESIGNED THE PROJECT |
| | SIGN OR CEATE NEW PAGES WITH CHANGES |
| | CLOUDED OR DELTAS, SIGNED AND SEALED. |
| | |
| | 2) COMMENT 3A FROM LAST REVIEW:SHEET 4.1 |
| | WEST ELEVATION 4'-0" DIA. FIXED WINDOW |
| | SHALL BE 45 MINUTE OPENING PROTECTIVES, |
| | SHOP DRAWING AFTER THE PERMIT IS ISSUED |
| | WILL BE FINE. |
| | THE OTHER ISSUE WILL BE LARGE MISSLE IM- |
| | PACT, SHEET A-8 WINDOW (F) PROVIDE |
| | MISSLE IMPACT HEAVY GUAGE GALVANIZED |
| | EXPANDED METAL, PROVIDE PRODUCT TESTING, |
| | 140 MPH WINDS, EITHER STATE APPROVAL OR |
| | SITE SPECIFIC. |
| | |
| | 3) COMMENT 3B PREVIOUS REVIEW: |
| | SHEET A2.1 INDICATES DOOR OPENING NUMBER |
| | 126 WHICH HAS A LOUVER, 705.1.1.2 WILL |
| | REQUIRE A 45 MINUTE PROTECTIVE. |
| | |
| | 4) COMMENT 3C FROM PREVIOUS REVIEW: |
| | DISCREPANCY SEE SOUTH SERVICE YARD SHEET |
| | A2 INDICATES DOOR # 110 14-6 FROM PROPER |
| | TY LINE VS A2.2 14'-1", THE DISCREPANACY |
| | IS HOW FAR THE FRONT OF THIS WALL IS |
| | FROM THE PROPERTY LINE!!! |
| | |
| | 5) SINCE THERE IS NO ESTABLISHED PROP- |
| | ERTY LINE ON THE NORTH SIDE OF THE BUILD |
| | ING THIS SAME ISSUE OF OPENING PROTEC- |
| | TIVESWILL BE A ISSUE, PLANS INDICATE ASS |
| | UMED PROPERTY LINE OF 10'-6" AWAY FROM |
| | THE BUILDING. DOORS WILL REQUIRE 3/4 |
| | HR PROTECIVE, 2HR RATED WALL. PLANS INDI |
| | CATE THE FIRE RATING BUT HOW WILL THE |
| | LARGE MISSLE IMPACT RATING BE ACHIEVED? |
| | GLASS CAN NOT BE 45 MINUTE FIRE RESIS- |
| | TANT AND LARGE MISSLE IMPACT RATED AT |
| | THE SAME TIME. |
| | |
| | 6) COMMENT 6 FROM PREVIOUS REVIEW: |
| | PROVIDE FIRE SPRINKLER PLANS REQUIRED BY |
| | TABLE 500 ALLOWED AREA INCREASE FOR |
| | SPRINKLERED BUILDINGS AND 903.7.2.4. |
| | EVERY AUTOMATIC SPRINKLER SYSTEM |
| | REQUIRED BY THIS CODE SHALL CONFORM TO |
| | NFPA 13.903.2 REQUIREMENTS. |
| | |
| | PROVISO:PLANS NOW INDICATE THAT THERE |
| | WILL BE NO BLEACHERS IN THIS GYM!!!!! |
| | **REMOVE BLEACHERS FROM SHEET E3.** |
| | |
| | PROVISO: SHOP DRAWINGS FOR ACCESSIBLE |
| | SIGNAGE AND TO BE INSTALLED BEFORE THE |
| | CERTIFICATE OF OCCUPANCY WILL BE ISSUED. |
| | |
| | 7) COMMENT 14 PREVIOUS REVIEW DOOR SCHED |
| | ULE HADN,T INDICATED WHAT DOORS REQUIRE |
| | PANIC HARDWARE.SHEET A8 NOW DOES INDI- |
| | CATE PANIC HARDWARE, DOORS 1/116 & 7/116 |
| | INDICATE PANIC HARDWARE, AS IN THE MEET- |
| | ING THESE DOORS LEAD TO GATED SERVICE |
| | YARDS, NOT A EGRESS. 9035.1.2 FIRE ALARM |
| | BOXES ARE NOT TO BE MORE THAN 5'-0" |
| | FROM AN EXIT, REMOVE THE STROBE AND |
| | HORN FROM LS1. |
| | |
| | 8) COMMENT 13 FROM 1ST REVIEW: |
| | SHEET A6.3 WALL SECTIONS, DETAILS DO NOT |
| | GIVE STUD SPACING, GUAGE, NOR THE WIRE |
| | SIZE & SPACING, HOW ARE STUDS TO BE |
| | SECURED TO THE STRUCTURE ABOVE. |
| | |
| | 9) FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) WINDOWS FIXED & OPERATABLE |
| | B) EXT DOORS, SOLID & GLAZED |
| | C) LOUVERS |
| | D) ROOF ASSEMBLIES, ALL TYPES USED |
| | E) STORM SHUTTERS |
| | F) TRUSS ANCHORS |
| | *******IMPORTANT******** |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |