| 2004-02-25 00:00:00 | ****CORRECTIONS**** |
| | |
| | PAID PLAN REVIEW, NOT A PERMIT APP. |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)THIS WILL BE A THRESHOLD BUILDING |
| | AS DEFINED IN FBC105.13 AND WILL REQUIRE |
| | A THRESHOLD INSPECTOR AND A THRESHOLD |
| | INSPECTION PLAN PRIOR TO PERMITTING. |
| | |
| | 2.)SOME SHEETS HAVE A PHOTOCOPY OF |
| | A SEAL AND SIGNATURE.ALL SIGNATURES |
| | ARE TO BE ORIGINAL WITH A RAISED SEAL. |
| | THE PRINTED NAME AND LICENSE NUMBER OF |
| | THE PERSON SEALING THE DOCUMENT IS TO |
| | BE INCLUDED ON THE SHEET, FAC61G15-23, |
| | FAC61G1-16.003, 004. |
| | |
| | 3.)PROVIDE A SOILS INVESTIGATION |
| | REPORT. |
| | |
| | 4.)THE 3' DIMENSION ON A1.1 POINTS TO |
| | A DIMENSION LINE THAT ENCROACHES THE |
| | PROPERTY LINE.NOTE THAT A 3' SETBACK |
| | FROM THE PROPERTY LINE WOULD REQUIRE A |
| | 3 HR WALL AS PER TABLE 600.IT MUST BE |
| | OVER 3' TO REQUIRE A 2 HR WALL AS |
| | INDICATED ON THE PLAN.REVISE ALL |
| | SHEETS NECESSARY TO REFLECT A DIMENSION |
| | OF GREATER THAN 3', OR CHANGE THE |
| | STRUCTURAL DETAILS TO COMPLY WITH |
| | TABLE 600. |
| | |
| | 5.)REVISE THE BUILDING DATA, ITEM #3, |
| | LS1 TO CORRECTLY REFLECT THE FIRE |
| | RESISTANCE RATINGS. |
| | |
| | 6.)PRODUCT APPROVALS NOT SUBMITTED |
| | BEFORE ISSUANCE OF THE PERMIT WILL |
| | REQUIRE SEPARATE PERMITS WITH SEPARATE |
| | FEES. |
| | |
| | 7.)SEE PREVIOUS LIST REGARDING THE |
| | DOOR HARDWARE AND THE BLEACHERS.A |
| | TRANSMITTAL LETTER REFERS TO A |
| | SPECIFICATION SECTION AND BLEACHER |
| | SECTION.I WAS UNABLE TO FIND THESE ON |
| | THE PLAN.THE GYMNASIUM EQUIPMENT |
| | SPECIFICATIONS PROVIDED DO NOT SHOW |
| | COMPLIANCE WITH FBC1012 AND 1019.7 |
| | (HARDWARE).PLEASE REVISE THE PLAN. |
| | |
| | 8.)COMPLIANCE WITH TABLE 600 SHOULD |
| | BE INDICATED ON THE STRUCTURAL AND |
| | ARCHITECTURAL SHEETS AS WELL AS LS1. |
| | |
| | 9.)LS1, PROVIDE THE DISTANCE TO THE |
| | PROPERTY LINE FOR THE 1 HR WALL.PLANS |
| | ARE TO BE TO SCALE, FBC104.2.1. |
| | |
| | 10.) PLEASE NOTE THAT THE UL LISTING |
| | PROVIDED FOR THE 1 HR WALL (LS1) REFERS |
| | TO U905, WHICH IS 2 HR.DETAILS WHICH |
| | EXCEED CODE REQUIREMENTS ARE |
| | ACCEPTABLE; THIS NOTE IS ADVISORY ONLY. |
| | |
| | 11.)HETAL16, 3-S5, FASTENING CONFLICTS |
| | WITH CATALOG.USE HIGH-WIND CATALOG |
| | WHICH INCLUDES UPDATED LOADS RELATED TO |
| | STRESS INCREASES FOR STEEL, AND CHECK |
| | ALL CONNECTORS.CALCULATIONS FOR THE |
| | ALTERNATE FASTENING MAY BE SUBMITTED IN |
| | LIEU OF CHANGING THE PLAN. |
| | |
| | 12.)WHEN RESUBMITTING, PLEASE SUBMIT |
| | OLD SHEETS SEPARATELY FOR REFERENCE. |