| Date |
Text |
| 2003-06-19 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | AMENDMENTS TO FBC, CHAPTER 1, |
| | ADMIN. CODE. |
| | |
| | 1) SHT- LS1, 2001 PLUMBING CODE MINIMUM |
| | FIXTURE CALCULATIONS. 9 WATER CLOSETS |
| | ARE REQUIRED. SHOWS ONLY 7 PROVIDED. |
| | TABLE 403.1 |
| | 2) SHT A-2 CONCESSIONS FOOD SERVICE. |
| | PLEASE CONTACT PALM BEACH COUNTY HEALTH |
| | UNIT 901 EVERNIA STREET WPB FOR REVIEW |
| | PRIOR TO RESUBMITTING PLANS WITH THE |
| | CITY FOR REVIEW. (561) 355-3018 |
| | SECTION 101.4.7 |
| | 3) CONTACT RODNEY COMPO - INDUSTRIAL |
| | PRE-TREATMENT, ENVIRONMENTAL COMPLIANCE |
| | TO DETERMINE THE SIZE OF GREASE TRAP RE- |
| | QUIRED. |
| | 4) SHTS A2 & A5 TURNING CIRCLE REQUIRED |
| | IN TOILET ROOM NOT HDCP STALL. SECTION |
| | 11-4.22.3 |
| | 5) SHT A10 DETAIL #3 SHOW URNAL HEIGHT |
| | 11-18.2, AND CLEAR FLOOR SPACE 11-4.18.3 |
| | 6) SHT A10 SHOWER DETAILS REQUIRED. SEC |
| | 11-4.21. SHOW GRAB BAR HEIGHT 4-21.4, |
| | CONTROLS 4.21.5, CURBS 4.21.7 ECT. |
| | 7) SHT P-1 PLUMBING NOTES #1, & #2, FBC |
| | NOT STANDARD CODE IS IN EFFECT. PLEASE |
| | CHANGE REFERENCE. |
| | 8) SHT P-1 PLUMBING NOTES #5, AIR CHAMB- |
| | ERS NOT APPROVED. DELETE FROM REFERENCE. |
| | 9) SHT P-1 PLUMBING NOTES #10 RPZ BACK- |
| | FLOW REQUIRED. 608.13.2 |
| | 10) SHT P-1 WATER HEATER DETAIL, THERMAL |
| | EXPANSION CONTROL REQUIRED. 607.3.2 |
| | 11) SHT P-2 ROOF CALCULATIONS FOR RD-2, |
| | SHT A-3 INDICATES 38'X 6' (1/2 OF 12' |
| | HEIGHT) = 228 SQ.FT., PLUS 38'X.75 FOR |
| | THE PARAPET = 28'6". TOTAL 256'6". NOT |
| | SHOWN IN CALCULATIONS IS THE 1/2 THE |
| | AREA OF THE VERTICAL WALL, AND THE AREA |
| | OF THE ROOF THAT DRAINS DOWN TO RD-2 |
| | FROM THE EAST ENTRY PORCH. THIS IS TYPI- |
| | CAL FOR RD-3, AND RD-4. PLEASE CLAIRFY. |
| | SHOW THIS INFORMATION FOR THESE AREAS |
| | FOR ROOF DRAINS IN QUESTIONS. |
| | 12) PROVIDE A STORM RISER DIAGRAM PER |
| | SECTION 104.2.1 |
| | 13) SUBMIT CALCULATIONS FOR THE MAIN |
| | GYM ROOF AREA. SIZE GUTTERS PER TABLE |
| | 1106.6, SHOW SLOPE OF GUTTER. INDICATE |
| | NUMBER OF DOWNSPOUTS. (SHT A4.1 SHOWS |
| | ONLY ONE DOWNSPOUT) SHOW SIZE OF DOWN- |
| | SPOUT.TABLE 1106.2 |
| | 14) SHT P-3 DETAIL #4 WATER ROSER DIA- |
| | GRAM, AIR CHAMBERS ARE NOT APPROVED. DE- |
| | LETE FROM RISER DIAGRAM. 604.9 |
| | *********WHEN RESUBMITTING PLANS******** |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |