| Plan Review Notes For Permit 03060496 |
| Permit Number |
03060496 |
|
| Review Stop |
E |
| Sequence Number |
7 |
|
| Notes |
| Date |
Text |
| 2004-02-27 00:00:00 | **** REDLINED OCP SHOWN FOR 9.2KW AHU. | | | PLEASE SEE NEC 424.3B, MIN OCP 125%. | | | SHOWN AS 2P-40, SHOULD BE A MIN OF 2P- | | | 50. | | | PLEASE VERIFY LOAD AND RATING ON NAME- | | | -PLATE OF UNIT. |
|