Text |
| 2004-02-13 00:00:00 | ************* UNSAT ************ |
| | |
| | 1)NOTE: PLEASE SEE PLANS, HAND DRAWN |
| | CHANGES HAVE BEEN MADE TO PLANS. PLANS |
| | CONTAIN WHITE-OUT. |
| | PLANS MUST BE REPRINTED AND AND THEN |
| | SIGNED, DATED AND SEALED BY THE ENGINEER |
| | OF RECORD. |
| | PREVIOUSLY NOTED. |
| | |
| | 2)NOTE: PLEASE HAVE PLANS "SIGNED" BY |
| | THE ENGINEER WITH A COMPLETE "SIGNATURE" |
| | AS REQ'D UNDER FS 471.025 AND FAC 61G15- |
| | -23.002. PER RULING OF FBPE'S IN OCT 03, |
| | INITIALS ARE NOT ACCEPTABLE UNLESS |
| | PE LICENSE FROM STATE WAS SIGNED LIKE |
| | THIS. IF WHAT APPEARS TO BE INITIALS |
| | ARE INDEED "SIGNATURE" PLEASE PROIDE |
| | COPY OF FL PE LICENSE AND DRIVERS LIC., |
| | CONTAINING SIGNATURE. |
| | |
| | 3)NOTE: PLEASE SEE SD NOTE: ON E-1, |
| | DOES NOT SEEM TO CORRELATE WITH PLANS |
| | AND CIRCUITING. |
| | PLEASE SEE NFPA-72 8-1.4.2, SD' THAT |
| | ARE W/IN 20' OF COOKING APPLIANCE MUST |
| | BE EQUIPPED WITH AN ALARM SILENCING |
| | MEANS OR OF THE PHOTOELECTRIC TYPE. |
| | |
| | 4)NOTE: PLEASE CORRELATE LOADS SHOWN |
| | FOR A/C. PANEL SHOWS ONE AND LOAD CALCS |
| | SHOW ANOTHER. |
| | PLEASE CLARIFY NO A/C IN OTHER UNIT?? |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |