| Date |
Text |
| 2003-06-27 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 11 |
| | |
| | 1) SHT A.2 BATHROOM SHALL COMPLY SECTION |
| | 11-4.23 AND ALL SUBSECTIONS. PROVIDE |
| | DETAILS. 4TH FLOOR BUSINESS TENANT. |
| | 2) SHT A.2 FOURTH FLOOR BUSINESS TENANT, |
| | PER TABLE 403.1 A DRINKING FOUNTAIN IS |
| | REQUIRED. ALSO SEE SECTION 410.1 |
| | 3) SHT A.2 5TH FLOOR SOUTH RESIDENTIAL, |
| | PER TABLE 403.1 A WASH MACHINE CONNECT- |
| | ION IS REQUIRED. |
| | 4) SHT A.2 ROOF PLAN, SUBMIT CALCULAT- |
| | IONS FOR PRIMARY AND SECONDARY ROOF |
| | DRAINS. SHOW 1/2 AREA FOR ALL VERTICAL |
| | WALLS INCLUDING PARAPETS. SHOW SLOP OF |
| | ROOF TO DRAINS. SECTIONS 1106 & 1107 AND |
| | ALL SUBSECTIONS. |
| | 5) SHT P-1 KEY NOTES: #11, THE RELIEF |
| | VALVE SHALL DISCHARGE FULL SIZE. SECTION |
| | 504.7.1. - #9 MINIMUM EMERGENCY PAN |
| | DRAIN SIZE IS 3/4". SECTION 504.8.1 |
| | SHT P-1 WATER RISER DIAGRAM, AIR CHAMB- |
| | ERS ARE NOT APPROVED. WATER HAMMER AR- |
| | RESTORS REQUIRED BY 604.9 SHALL BE LOCA- |
| | TED AT WASH MACHINES, ICE MAKERS, AND |
| | DISHWASHERS. |
| | 6) ALL ABANDONED/DEMO'ED PIPING SHALL BE |
| | INSPECTED PRIOR TO COVERING. |
| | 7) SHT P-1 GENERAL NOTES: #16, AIR |
| | CHAMBERS ARE NOT APPROVED. DELETE REFER- |
| | ENCE. |
| | 8) SHT P-1 SUBMIT RISERS FOR THE RELIEF |
| | VALVE DISCHARGE LINE AND THE EMERGENCY |
| | PAN DRAIN LINE. SHOW PIPE SIZE, TYPE OF |
| | MATERIAL, AND TERMINATION POINT. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |