| 2003-06-25 00:00:00 | ******CORRECTIONS******* |
| | |
| | SAMANTHA THYNG, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)BEDROOMS ARE REQUIRED TO HAVE |
| | EMERGENCY EGRESS FBC1005.4.A 38" HIGH |
| | SINGLE HUNG WINDOW DOES NOT COMPLY. |
| | |
| | 2.)THE WINDOW AT THE TUB LOCATION |
| | MUST COMPLY WITH FBC2405.2. |
| | |
| | 3.)ADDITIONS OVER 25% MUST COMPLY |
| | WITH FBC 3401.7.1.2.1. |
| | |
| | 4.)SUBMIT TWO COPIES OF PRODUCT |
| | APPROVALS FOR MULLIONS AND SHINGLES. |
| | THE SHINGLE PRODUCT APPROVAL MAY BE |
| | SUBMITTED WITH THE ROOF PERMIT |
| | APPLICATION. |
| | |
| | 5.)SEPARATE PERMITS REQUIRED. |
| | |
| | 6.)ENERGY CALCS REQUIRED FBC13-101.2. |
| | |
| | 7.)HOW IS THE BASE PLATE ATTACHED |
| | TO THE CONCRETE?GIVE ATTACHMENT SIZE |
| | AND TYPE, EMBEDMENT, DISTANCE. |
| | |
| | 8.)PROVIDE A ROOF SHEATHING ATTACHMENT |
| | SCHEDULE. |
| | |
| | 9.)IT IS UNCLEAR WHICH HETA ATTACHMENT |
| | IS SPECIFIED ON THE WALL SECTION. REVISE |
| | AND GIVE DESIGN UPLIFT FOR ALL |
| | ATTACHMENTS WITH STRUCTURAL CALCULATIONS |
| | OR SEALED BY AN ENGINEER, FBC104.3.1.1. |
| | |
| | 10.)FIRESTOP REQUIRED FBC 705.3. |
| | |
| | 11.)ATTIC ACCESS REQUIRED FBC2309.6. |
| | |
| | 12.)ADDITIONAL FEES REQUIRED, $4.48. |
| | |
| | 13.)PROVIDE A ROOF FRAMING PLAN. |
| | |
| | 14.)DESIGN INFORMATION IS REQUIRED |
| | TO BE ON THE PLAN, FBC 1606.1.7. |
| | |
| | 15.)THE SECOND SHEET HAS A BLANK |
| | TITLE BLOCK. |
| | |
| | 16.)ALL CHANGES MUST BE APPROVED BY |
| | HISTORIC BEFORE RESUBMITTAL. |
| | |
| | CLOUD ALL CHANGES BEFORE RESUBMITTAL. |
| | PROVIDE A WRITTEN RESPONSE TO ALL ITEMS |
| | EXPLAINING HOW IT HAS BEEN ADDRESSED. |