| Plan Review Notes For Permit 03060481 |
| Permit Number |
03060481 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-06-19 00:00:00 | *************** UNSAT *************** | | | | | | 1)NOTE: PLEASE CORRELATE ELECTRICAL | | | DIAGRMA WITH EQUIPMENT BEING INSTALLED. | | | HEAT PUMP NOT SHOWN ON RISER? | | | WIRE/CONDUIT ETC. | | | | | | 2)NOTE: PLEASE SUBMIT LOAD CALCULATIONS | | | WITH EXISTING AND NEW LOADS. | | | PLEASE SHOW SIZE OF EXISTING SERVICE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|