| 2003-11-06 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FLORIDA STATUTES | | | FLORIDA ADMINISTRATIVE CODE | | | | | | A) COMMENTS FROM PREVIOUS RESPONSE NOTED | | | BUT A CLAIRFICATION OF COMMENTS NEEDED. | | | 1) A SEPARATE BACKFLOW IS REQUIRED FOR | | | THE MARINA WATER SERVICE LINE. SECTION | | | 608.13.2 | | | 2) MANUFACTURE SPECIFICATION SHEETS TO | | | BE SUBMITTED FOR REVIEW FOR THE PUMP-OUT | | | SYSTEM. SECTION 104.3.1 | | | 3) MANUFACTURE SPECIFICATION SHEETS TO | | | BE SUBMITTED FOR REVIEW FOR THE UTILITY | | | PEDESTALS, (DETAIL #14). SECTION 104.3.1 | | | 4) NEW COMMENT: ENGINEERS SHALL LEGIBLY | | | THEIR NAME, ADDRESS AND LICENSE NUMBER | | | ON EACH SHEET. IF PRACTICING THROUGH A | | | DULY AUTHORIZED ENGINEERING BUSINESS, | | | ENGINEERS SHALL LEGIBLY INDICATE THEIR | | | NAME AND LICENSE NUMBER, AS WELL AS, THE | | | NAME, ADDRESS, AND CERTIFICATE OF | | | AUTHORIZATION NUMBER OF THE ENGINEERING | | | BUSINESS ON EACH SHEET. 61G15-23.002(2) | | | FS471.025 - (SEE ATTACHED SHEET). | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|