Plan Review Notes
Plan Review Notes For Permit 03060449
Permit Number 03060449
Review Stop P
Sequence Number 1
Notes
Date Text
2003-06-27 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
  
  
 1) SHT C3 OF 5 - RPZ BACKFLOW REQUIRED
 SECTION 608.13.2
 2) SHT C3 OF 5 AND SHT C5 OF 5 MANUF.
 INFORMATION REQUIRED FOR PUMP-OUT SYSTEM
 3) SHT C3 OF 5 MANUF. INFORMATION REQ-
 UIRED FOR UTILITY PEDESTALS, (DETAIL #4)
 4) ALL PVC EXPOSED TO ULTRA VIOLET RAYS
 SHALL BE PROTECTED BY PAINTING WITH
 APPROVED U.V. BLOCKING PAINT PER MANUF.
 INSTALLATION REQUIREMENTS.
  