| 2003-07-29 00:00:00 | *******CORRECTIONS******** |
| | |
| | 1.)SEPARATE PERMITS REQUIRED. |
| | |
| | 2.)WHEN RESUBMITTING, REPLACE VOIDED |
| | SHEETS WITH THE NEW SHEETS.SUBMIT THE |
| | VOIDED SHEETS SEPARATELY. |
| | |
| | 3.)THE ENERGY CALC GIVES A SQUARE |
| | FOOTAGE OF 844.THE BUILDING DATE, A1, |
| | SHOWS 1021.EITHER CORRECT OR CLARIFY |
| | AS TO HOW YOU GOT THE 844 NUMBER.ALSO |
| | SIGN THE OWNER/AGENT LINE OF THE ENERGY |
| | CALC PER FBC13-101.2. |
| | |
| | 4.)PROVIDE A SOILS INVESTIGATION |
| | REPORT. |
| | |
| | 5.)THIS PARCEL IS IN A FLOOD ZONE. AS |
| | PER CITY OF WEST PALM BEACH MUNICIPAL |
| | CODE 94-546(B)(2), THE LOWEST FLOOR IS |
| | TO BE ELEVATED 6" ABOVE THE BASE FLOOD |
| | ELEVATION. |
| | |
| | 6.)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE PLANS MUST BE STAMPED |
| | AND THE ORIGINAL RECEIPT ATTACHED TO THE |
| | APPLICATION.233-5025 |
| | |
| | 7.)ADDITIONAL FEES DUE (RADON, VALUE |
| | ADJUSTMENT). |
| | |
| | 8.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 9.)THE STAIR RAILING MUST COMPLY WITH |
| | FBC1608.2.1.1, FBC1007.5. |
| | |
| | 10.)THE GUARDRAIL MUST COMPLY WITH |
| | FBC1608.2.2.1, FBC1026.5. |
| | |
| | 11.)THE STAIR MUST COMPLY WITH FBC |
| | 1007.8.2.3. |
| | |
| | 12.)REGARDING NOTES 9, 10 AND 11, |
| | NOTE ON PLAN.SHOP DRAWINGS TO BE |
| | SUBMITTED PRIOR TO INSTALLATION. |
| | |
| | 13.)PROVIDE TWO LEGIBLE COPIES OF |
| | PRODUCT APPROVALS FOR: |
| | STANDING SEAM ROOF (MAY BE SUBMITTED |
| | WITH ROOF PERMIT) |
| | FRENCH DOOR |
| | IMPACT PROTECTION FBC1606.1.4 |
| | GLASS BLOCK |
| | |
| | 14.)ZONING APPROVAL REQUIRED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 15.)EMERGENCY EGRESS FOR SLEEPING |
| | ROOMS REQUIRED FBC1005.4. |
| | |
| | SAMANTHA THYNG, BUILDING PLANS EXAMINER |
| | [email protected] |