| Notes |
| Date |
Text |
| 2003-06-20 00:00:00 | ********* PROVISO/ REVISION NEEDED**** | | | | | | 1)NOTE: PLANS AND PANEL SCHEDULE SHOW | | | TWO A/C SYSTEMS AND LOAD CALCS ONLY | | | SHOW ONE HEAT STRIP @ 65%. | | | | | | 2)NOTE: PLEASE SEE MISSING LOAD AND OCP | | | ON PANEL SCHEDULE FOR 2ND AHU HEAT. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW BEFORE ROUGH ELECTRICAL INSPECT- | | | -ION IS CALLED IN. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|