| 2005-05-19 00:00:00 | ****CORRECTIONS**** | | | TRUSS SUBMITTAL | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)SEE ATTCHED FROM THE SIMPSON | | | CATALOG.THE LOADS ON THE CONNECTOR | | | SCHEDULE PROVIDED ARE HIGHER THAN THE | | | CATALOG.ALSO, WHAT IS THE LAST COLUMN, | | | WIND (133)? | | | | | | 2.)APPARENTLY THE EOR HAS REDLINED THE | | | FLOOR LOADING.THE LOADING REQUIRED BY | | | EOR IS HIGHER THAN THE LOADS INDICATED | | | IN THE ENGINEERING. | | | | | | 3.)A TITLE BLOCK IS REQUIRED ON THE | | | TRUSS ENGINEERING, FAC61G15-23.002. | | | |
|