2004-01-28 00:00:00*****CORRECTIONS******
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE PREVIOUS LISTS IN REGARDS TO
 PRODUCT APPROVALS.ANY TEST REPORTS
 REQUIRED BUT NOT SUBMITTED WILL REQUIRE
 SEPARATE PERMITS.
  
 2.)THE NOTICE OF COMMENCEMENT IS
 EXPIRED (90 DAYS WITHOUT COMMENCING
 WORK), FS713.13.THIS MAY BE PROVIDED
 AT TIME OF PERMIT ISSUANCE.
  
 3.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025 FOR MORE
 INFORMATION.
  
 4.)SEE PREVIOUS LIST, ITEM #5.THE
 PLANS STILL SHOW CASEMENT WINDOWS.
 SEE THE WINDOW SPRINKLER DOCUMENTATION;
 FIXED GLASS ONLY ALLOWED.
  
 5.)SEE ATTACHED NOTICE IN REGARDS TO
 FS553.80(2)(B).A 4X FEE HAS BEEN
 CHARGED (REQUEST FOR SPRINKLER PLANS
 NOT ADDRESSED THREE TIMES).SEE ITEM
 #5 ABOVE.THIS IS THE SECOND TIME THAT
 THIS CORRECTION HAS BEEN MADE.A
 SECOND 4X FEE WILL BE CHARGED IF THIS
 IS NOT ADDRESSED ON THE NEXT REVIEW.
 SEE ATTACHED BZ235301.
  
 6.)BEFORE RESUBMITTING, HAVE ANY
 REVISED SHEETS STAMPED BY THE HISTORIC
 PRESERVATION DIVISION.
  
 7.)THE HYDRAULIC CALCULATIONS ARE
 REQUIRED TO HAVE THE ENGINEER'S
 INFORMATION INCLUDED ON THE COVER
 SHEET.
  
 8.)THE MODEL WS SPRINKLER HEAD IS
 REQUIRED TO BE A MINIMUM OF 6' FROM
 STANDARD SPRINKLER HEADS, SEE 2ND FLOOR
 PLAN.