Plan Review Notes
Plan Review Notes For Permit 03060274
Permit Number 03060274
Review Stop FIRE
Sequence Number 4
Notes
Date Text
2003-10-30 00:00:001) FIRE ALARM NOTES # 11 INDICATES
 A SUPERVISORY SIGNAL UPON ACTIVATION
 OF DUCT SMOKE DETECTORS. ACTIVATION
 OF ANY DUCT SMOKE DETECTOR SHALL
 CAUSE THE FIRE ALARM SYSTEM TO ACTIVATE.
  
 2) BUILDING ADDRESS REQUIRED ON PROPER
 ELEVATION.
  
 3) FIRE ALARM CIRCUITS SHALL BE CLASS A
 OR FULLY ADDRESSABLE.
  
 4) SECURITY LOCKS CONNECTED TO THE
 FIRE ALARM SYSTEM SHALL COMPLY WITH
 EITHER ACCESS CONTROL OR DELAYED
 EGRESS REQUIREMENTS.