2003-11-07 00:00:00THIS IS THE FOURTH REQUEST FOR THE
 DESIGN INFORMATION OF THE FIRE
 PROTECTION SYSTEM TO BE PROVIDED THE
 PLANS.
  
 THE CARRIBBEAN FIRE & ASSOCIATES
 HYDRAULIC CALCULATIONS DO NOT COMPRISE
 A DESIGN.SEE NFPA 13-99 CHAPTER 8,
 SECTION 8-1.1.1 AND THE FLORIDA
 ADMINISTRATIVE CODE CHAPTER 61G15-32
 RESPONSIBILITY RULES OF PROFESSIONAL
 ENGINEERS CONCERNING THE
 DESIGN OF FIRE PROTECTION SYSTEMS.
  
 THE PLANS DO NOT REFLECT ACCOMODATION OF
 THE TYCO/CENTRAL SPRINKLER HEADS AS
 DESCRIBED IN THE TWO CUT SHEETS
 PROVIDED.
  
 AN ACCEPTABLE INSTALLATION METHOD IS
 THAT CONTAINED IN THE NER REPORT #516
 AND THE MANUFACTURER'S PUBLISHED
 INSTRUCTIONS.
  
 SOME OF THE EXISTING CONFLICTS ARE:
 1) OPERABLE WINDOWS, THE DESIGN REQUIRES
 FIXED GLASS.
 2) HORIZONTAL MULLIONS, THE DESIGN DOES
 NOT ALLOW THEM.
 3) DELUGE HEADS ON THE EXTERIOR AND
 INCLUDED IN THE MOST DEMANDING AREA OF
 THE HYDRAULIC CALCUALATIONS.
  
 SEE NOTES #2 & #6 ON THE 8/26/03 LIST.