| Plan Review Notes For Permit 03060274 |
| Permit Number |
03060274 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2003-09-04 00:00:00 | 1) TACTILE SIGNAGE REQUIRED AT STAIRS. | | | | | | 2) ALL SHAFTWAYS THAT PERSONS CAN FALL | | | INTO MUST BE MARKED "SHAFTWAY" WITH | | | 6" HIGH LETTERS. | | | | | | 3) SIGNS ARE REQUIRED AT ELEVATORS | | | DO NOT USE ELEVATORS IN THE EVENT OF | | | A FIRE. | | | | | | 4) SINCE FIRE ALARM PERMITS ARE EXPECTED | | | AFTER AUGUST 1, 2003, THE FIRE ALARM | | | SYSTEM IS EXPECTED TO MEET UL LISTED | | | FOR CENTRAL STATION SERVICE SINCE THE | | | PERMIT APPLICATION WILL FALL AFTER | | | THE AUGUST 1, 2003, IMPLEMENTATION DATE. | | | | | | 5) IT APPEARS THAT SMOKE DETECTORS ARE | | | INSTALLED IN THE KITCHENS. SMOKE | | | DETECTORS ARE NOT INSTALLED IN KITCHENS | | | AREAS. IT DOES APPEAR THAT THE DESIGNER | | | IS TRYING TO MEET THE INTENT OF | | | SMOKE DETECTORS INSIDE AND OUTSIDE | | | THE SLEEPING ROOMS BUT WHAT PREVENTS | | | FALSE OR NUISANCE ALARMS. ALSO ARE | | | THESE SMOKE DETECTORS SINGLE STATION | | | AS REQUIRED OR ARE THEY PLANNED TO | | | BE CONNECTED TO THE FIRE ALARM SYSTEM. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|