2003-09-04 00:00:001) TACTILE SIGNAGE REQUIRED AT STAIRS.
  
 2) ALL SHAFTWAYS THAT PERSONS CAN FALL
 INTO MUST BE MARKED "SHAFTWAY" WITH
 6" HIGH LETTERS.
  
 3) SIGNS ARE REQUIRED AT ELEVATORS
 DO NOT USE ELEVATORS IN THE EVENT OF
 A FIRE.
  
 4) SINCE FIRE ALARM PERMITS ARE EXPECTED
 AFTER AUGUST 1, 2003, THE FIRE ALARM
 SYSTEM IS EXPECTED TO MEET UL LISTED
 FOR CENTRAL STATION SERVICE SINCE THE
 PERMIT APPLICATION WILL FALL AFTER
 THE AUGUST 1, 2003, IMPLEMENTATION DATE.
  
 5) IT APPEARS THAT SMOKE DETECTORS ARE
 INSTALLED IN THE KITCHENS. SMOKE
 DETECTORS ARE NOT INSTALLED IN KITCHENS
 AREAS. IT DOES APPEAR THAT THE DESIGNER
 IS TRYING TO MEET THE INTENT OF
 SMOKE DETECTORS INSIDE AND OUTSIDE
 THE SLEEPING ROOMS BUT WHAT PREVENTS
 FALSE OR NUISANCE ALARMS. ALSO ARE
 THESE SMOKE DETECTORS SINGLE STATION
 AS REQUIRED OR ARE THEY PLANNED TO
 BE CONNECTED TO THE FIRE ALARM SYSTEM.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL