| Notes |
| Date |
Text |
| 2003-09-08 00:00:00 | ********** NOTE *************** | | | | | | PLEASE SEE FIRE REVIEW COMMENTS. | | | SD'S MUST BE 3'FROM KITCHEN DOOR/OPENING | | | WHICH THEY APPEAR TO BE. NFPA-72 2-5.2.1 | | | .6. PLEASE GET WITH MIKE CARSILLO ON | | | SD PLACEMENT AND PERHAPS HEAT DETECTORS | | | PERMITTTED IN SD'S PLACE? | | | | | | ELECTRICAL PLANS SEEM TO BE OK. | | | PLEASE SEE RISER, SHOWS ALL SUB PANELS | | | AS 125A,PANELS ARE SHOWN AS 100A AND 42 | | | CIRCUIT. PLEASE CORRELATE RISER AND | | | PANELS. PLEASE ALSO NOTE, 100A AND 125A | | | PANELS DO NOT COME W/ 42 CIRCUITS. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION, | | | PLEASE SEE FIRE COMMENTS FOR ELEC SHEETS | | | PLEASE SEE THAT ELECTRICAL PLANS FOR THE | | | MOST PART ARE OK. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | PLEASE CALL FOR ANY QUESTIONS ABOUT SD'S | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|