Plan Review Notes
Plan Review Notes For Permit 03060274
Permit Number 03060274
Review Stop B
Sequence Number 3
Notes
Date Text
2003-08-26 00:00:001THE REQUESTED SIGNED SEALED AND
 DATED SURVEY HAS NOT BEEN PROVIDED.
  
 2THIS IS THE THIRD REQUEST FOR THE
 FIRE SPRINKLER PROTECTION DESIGN.THE
 ARCHITECT'S LETTER DATED 8/18/03
 DECLARING COMMENTS 1, 2 & 3 ARE THE
 CONTRACTOR'S RESPONSIBILITY IS NOT
 WITHSTANDING.FLORIDA STATUTE 553.80
 (2) (B) REQUIRES A FEE TO BE PAID OF
 FOUR TIMES THE AMOUNT OF THE PLAN
 REVIEW PORTION EACH TIME AFTER THE
 THIRD REVIEW. THIS IS IN ADDITION TO
 ANY OTHER FEES THAT MAY BE DUE.SEE
 THE ATTACHED NOTICE AND FBC 104.3.1.1
 #5.
  
 3THIS IS THE THIRD REQUEST FOR THE
 FIRE DESIGN NUMBER OF THE "NEW"
 EXTERIOR MASONRY WALLS AND INFILL AREAS.
 THE ARCHITECTS CITATION FOR THE
 EXISTING WALLS IS NOTED.SEE FBC
 701.5.1.
  
 4AS PREVIOUSLY NOTED, FBC TABLE 600
 REQUIRES "THREE" HOUR FIRE RATING FOR
 EXTERIOR WALLS LOCATED 0' - 3' FROM A
 COMMON PROPERTY LINE FOR TYPE V
 CONSTRUCTION, NOT THE DECLARED TWO HOUR.
 PLEASE REVISE AS NECESSARY AND SEE ITEM
 #3 ABOVE.
  
 5WITH THE ABOVE FIRE SPRINKLER DESIGN
 INFORMATION INCLUDE THE LISTING, TEST
 DATA FOR THE HEADS THAT WILL PROVIDE A
 TWO HOUR FIRE RATEDOPENING PROTECTION.
  
 6COMMENTS IN THE TWO PREVIOUS LISTS
 REMAIN WITH REGARDS TO IMPACT FEES,
 NOA'S FOR THE DOORS, WINDOWS AND ROOF
 COVERINGS, AND THE PROPRIETARY MASONRY
 IN THE U905DESIGN.THESE ARE NOT
 CAUSE FOR REJECTION BUT ADVISORY TO THE
 CONTRACTOR AND OWNER.