Text |
| 2003-08-26 00:00:00 | 1THE REQUESTED SIGNED SEALED AND |
| | DATED SURVEY HAS NOT BEEN PROVIDED. |
| | |
| | 2THIS IS THE THIRD REQUEST FOR THE |
| | FIRE SPRINKLER PROTECTION DESIGN.THE |
| | ARCHITECT'S LETTER DATED 8/18/03 |
| | DECLARING COMMENTS 1, 2 & 3 ARE THE |
| | CONTRACTOR'S RESPONSIBILITY IS NOT |
| | WITHSTANDING.FLORIDA STATUTE 553.80 |
| | (2) (B) REQUIRES A FEE TO BE PAID OF |
| | FOUR TIMES THE AMOUNT OF THE PLAN |
| | REVIEW PORTION EACH TIME AFTER THE |
| | THIRD REVIEW. THIS IS IN ADDITION TO |
| | ANY OTHER FEES THAT MAY BE DUE.SEE |
| | THE ATTACHED NOTICE AND FBC 104.3.1.1 |
| | #5. |
| | |
| | 3THIS IS THE THIRD REQUEST FOR THE |
| | FIRE DESIGN NUMBER OF THE "NEW" |
| | EXTERIOR MASONRY WALLS AND INFILL AREAS. |
| | THE ARCHITECTS CITATION FOR THE |
| | EXISTING WALLS IS NOTED.SEE FBC |
| | 701.5.1. |
| | |
| | 4AS PREVIOUSLY NOTED, FBC TABLE 600 |
| | REQUIRES "THREE" HOUR FIRE RATING FOR |
| | EXTERIOR WALLS LOCATED 0' - 3' FROM A |
| | COMMON PROPERTY LINE FOR TYPE V |
| | CONSTRUCTION, NOT THE DECLARED TWO HOUR. |
| | PLEASE REVISE AS NECESSARY AND SEE ITEM |
| | #3 ABOVE. |
| | |
| | 5WITH THE ABOVE FIRE SPRINKLER DESIGN |
| | INFORMATION INCLUDE THE LISTING, TEST |
| | DATA FOR THE HEADS THAT WILL PROVIDE A |
| | TWO HOUR FIRE RATEDOPENING PROTECTION. |
| | |
| | 6COMMENTS IN THE TWO PREVIOUS LISTS |
| | REMAIN WITH REGARDS TO IMPACT FEES, |
| | NOA'S FOR THE DOORS, WINDOWS AND ROOF |
| | COVERINGS, AND THE PROPRIETARY MASONRY |
| | IN THE U905DESIGN.THESE ARE NOT |
| | CAUSE FOR REJECTION BUT ADVISORY TO THE |
| | CONTRACTOR AND OWNER. |