2003-08-27 00:00:00FAILED:
 1. SHEET P-1 AND P-2 REFERS TO CIVIL
 DRAWING FOR EXACT LOCATION FOR
 CONNECTIONS AND CONTINUATION OF SANITARY
 , STORM WATER AND DOMESTIC WATER, NO
 CIVIL PLANS HAS BEEN PROVIDED.
 2. PLEASE NOTE THAT ANY NEW CONNECTIONS
 TO CITY SERVICES REQUIRES APPROVAL FROM
 PUBLIC UTILITIES & ENGINEERING,659-8040
 3. BACKFLOW ASSEMBLY MUST BE LOCATED ON
 PROPERTY AND LOACTION MUST BE APPROVED
 BY PUBLIC UTILITIES & ENGINEERING,
 659-8040.
 4. SHEET P-1, FIRST FLOOR PLAN-SANITARY,
 NOTE THAT STORM DRAIN LEADER SHUOLD BE
 CONNECTED TO STORM DRAINAGE AND
 SANITARY DRAIN TO SANITARY SYSTEMS,
 PLEASE VERIFY.
 5. KEYNOTES, NUMBRING THROUGHOUT THE
 BUILDING FROM FLOOR TO FLOOR NOT
 CONSISTENCE, SHEET P-1 AND P-2, PLEASE
 VERIFY.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI