Date Text
2003-07-29 00:00:00************** UNSAT *****************
  
 PLEASE ADDRESS COMMENTS BELOW. PLANS
 ARE COMING BACK FOR OTHER REVIEWERS.
  
 1)NOTE: PLEASE SEE 3W/ SQ FT STILL SHOWN
 AS ROUNDING DOWN ON UNITS B&C,
 PLEASE ALSO SEE LOAD FOR DRYER SHOWN
 AT 3KW. PLEASE SEE MIN PER 220-18
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]