Plan Review Notes
Plan Review Notes For Permit 03060274
Permit Number 03060274
Review Stop B
Sequence Number 2
Notes
Date Text
2003-07-29 00:00:001THE PROPERTY SURVEY'S PROVIDED ARE
 NOT SIGNED AND SEALED.PLEASE PROVIDE
 COPIES WITH ORIGINAL SIGNATURE AND
 EMBOSSED SEAL.
  
 2AS NOTED IN THE PREVIOUS CODE
 COMMENTS THE FIRE SPRINKLER SYSTEM
 DESIGN IS REQUIRED TO BE ON THE PERMIT
 PLANS.SEE FBC 104.3.1.1, #5.
  
 3THE ARCHITECT'S RESPONSE MEMO DATED
 7/18/03 REFERENCING A MEETING WITH THE
 BUILDING OFFICIAL IMPLIES THAT AN
 APPROVAL WAS GRANTED AT THAT TIME.IT
 WAS AND IS THE BUILDING OFFICIAL'S
 INTENTION THAT ANY CODE VARIANCES MAY
 COME ONLY THROUGH THE CITY'S
 CONSTRUCTION BOARD OF ADJUSTMENTS AND
 APPEALS FOR WHICH THERE IS AN
 OUTSTANDING APPLICATION DATED 3/03.
  
 THEREFORE THE TABLE 600 ISSUES REMAIN
 TO BE RESOLVED AS WELL AS THE
 EXTERIOR WALL RATINGS.
  
 4THE ORIGINAL PERMIT APPLICATION IS
 NOT INCLUDED WITH THE RE-SUBMITTED
 PLANS.
  
 5AS PREVIOULSY NOTED, THIS PROJECT IS
 SUBJECT IMPACT FEES COLLECTED BY THE
 COUNTY PRIOR TO PERMIT ISSUE.
  
 6SHEET A9.2, DESIGN # U905 REQUIRES
 THE BLOCK MANUFACTURER TO BE A UL
 CERTIFICATE HOLDER.PLEASE VERIFY THIS
 WITH YOUR VENDOR AND PROVIDE
 DOCUMENTATION TO THIS OFFICE.
  
 7IF TEST AND/OR NOTICE OF ACCEPTANCE
 REPORTS ARE NOT INCLUDED WITH THIS
 PERMIT APPLICATION FOR THE WINDOWS,
 DOORS AND ROOF COVERING, SEPARATE
 PERMITS, PLANS AND FEES WILL BE
 REQUIRED FOR THAT PORTION OF THE WORK.