Plan Review Notes
Plan Review Notes For Permit 03060274
Permit Number 03060274
Review Stop P
Sequence Number 1
Notes
Date Text
2003-06-25 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FBC-2001 CHAP. 1, AMENDMENTS
 ADMIN CODE
 FHA-98 DESIGN MANUAL
 FBC-2001 MECHANICAL
  
 1) SHT A2.1 FIRST FLOOR PLAN DETAIL #1.
 PER TABLE 403.1 A UNISEX TOILET ROOM
 COMPLYING WITH 11-4.22 AND A DRINKING
 FOUNTAIN ARE REQUIRED.
 2) SHT A2.1 SECOND FLOOR PLAN DETAIL #2,
 PER TABLE 403.1 AUTOMATIC CLOTHES WASHER
 CONNECTION REQUIRED. (ALSO SEE FOOTNOTE
 "F").
 3) SHT A5.1 SHOW CLEAR FLOOR SPACE ON
 TYPICAL TOILET ROOM PLAN DETAIL #1, AND
 TYPICAL KITCHEN PLAN DETAIL #3 PER FHA
 DESIGN MANUAL PAGE 7.43
 4) SHT A5.1 DETAIL #1 INDICATE MEASURE-
 MENT OFF TUB AND LAV TO CENTER LINE OF
 W/C. MINIMUM 18" REQUIRED OFF 1 FIXTURE
 OR THE OTHER AND MINIMUM OPENING REQUIR-
 ED IS 33". PLEASE SHOW OPENING SIZE.
 SEE FIGURES 1, 2, OR 3 PAGE 7.43 DESIGN
 MANUAL
 5) SHT P-1 DETAIL #03, SUBMIT CALCULAT-
 IONS FOR PRIMARY AND SECONDARY ROOF
 DRAINS PER SECTIONS 1106 & 1107 AND ALL
 SUBSECTIONS. CHECK OF NORTH SECTION OF
 ROOF SCALES OUT 47.83 FT TIMES 24.83 FT
 EQUALS 1,188 SQ.FT. NOT COUNTING 1/2
 AREA OF VERTICAL WALLS, INCLUDING PARA-
 PETS. (SECTION 1106.4). PLAN SHOWS 1,109
 SQ.FT. PLEASE CLAIRFY. SHOW CALCULATIONS
 FOR EACH AREA, NORTH, CENTER , & SOUTH.
 ALSO SHOW AREAS OF ROOF THAT DRAIN ONTO
 THE ROOF SECTIONS FROM ABOVE, I.E.
 STAIRWAYS & MECHANICAL ROOMS ECT. SECT-
 ION 1106.2
 6) SHT P-1 DETAIL #2, SECOND FLOOR SANT.
 STATES "EWH DRAIN LINE PROVIDE TRAP"
 PLEASE CLAIRFY, IS THIS A CONDENSATE
 LINE OR THE PAN DRAIN LINE FOR THE
 ELECTRIC WATER HEATER?
 7) SHT P-4 WATER ISOMETRIC, AIR CHAMBERS
 ARE NOT APPROVED. (TUB/SHOWER VALVES).
 DELETE FROM RISERS. WATER HAMMER ARREST-
 ORS AT WATER HEATERS SHALL BE LOCATED
 NEAR THE FIXTURE IN AN "EFFECTIVE RANGE"
 NOT IN THE CEILING. PDI-WH201 AND MANUF.
 INSTALLATION INSTRUCTIONS.
 8) SUBMIT RISER DIAGRAM FOR EMERGENCY
 PAN DRAINS FOR WATER HEATERS. SHOW PIPE
 SIZE AND INDICATE TYPE OF MATERIAL.
 SECTION 504.8, 504.8.1, & 504.8.2.
 9) SHT P-6 PLUMBING SPECIFICATIONS #2-M
 ADOPTED CODE IS FBC-2001 PLUMBING, NOT
 STANDARD CODE 1999 EDITION. CHANGE REF-
 ERENCE. - #3-L AIR CHAMBERS ARE NOT
 APPROVED. DELETE FROM REFERENCE. SECTION
 604.9- #4-F AIR CHAMBERS ARE NOT
 APPROVED. DELETE FROM REFERENCE.
 10) INDICATE ON PLANS IF SPECIFICATION
 "A" OR "B" WILL BE FOLLOWED FOR THE
 BATHROOMS IN EACH UNIT. PAGES 7.34 &
 7.35FHA DESIGN MANUAL.
 11) ARCHITECTURAL SHEETS - 61G1-16.004
 FIRM LICENSES NUMBER IS REQUIRED ON THE
 TITLE BLOCK
 12) SHT P-3 CONDENSATE DRAIN ISOMETRIC.
 UNABLE TO FIND THE REST OF THE CONDENS-
 ATE RISER DIAGRAM REFERED TO ON THE
 MECHANICAL PLANS. SUBMIT A COMPLETE
 CONDENSATE RISER DIAGRAM SHOWING ALL
 PIPE SIZES AND MATERIAL USED.
 13) SHT M-1 CONDENSATE FROM ROOF UNITS
 SHOW SOME DRAINING TO THE ROOF DRAINS,
 AND OTHERS DRAINING TO THE SECONDARY
 ROOF DRAINS. ALL SHALL DRAIN TO THE
 ROOF DRAINS. SECTION M307.2.1(3).
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692