2003-07-01 00:00:001) ALL DEMOLITION, RENOVATION, AND
 CONSTRUCTION SHALL COMPLY WITH NFPA 241.
  
 2) SUITABLE EXITS ARE TO BE PROVIDED
 DURING DEMOLITION, RENOVATION AND
 CONSTRUCTION ACTIVITIES.
  
 3) PLEASE INDICATE LOCATIONS OF ALL
 SMOKE DETECTORS CONTAINED WITHIN THE
 APARTMENTS. ELECTRIC POWERED SMOKE
 DETECTORS ARE REQUIRED INSIDE AND
 OUTSIDE OF ALL SLEEPING ROOMS.
  
 4) PLEASE PROVIDE MORE DETAILS ON NOTE
 19 ON PAGE A3.1. "PROVIDE TWO HOUR
 FIRE SPRINKLER HEADS (1 EXTERIOR, 1
 INTERIOR) ABOVE EACH WINDOW.
  
 5) PLEASE PROVIDE A NOTE ABOUT EGRESS
 WINDOWS. PLEASE EXPLAIN EXEPTIONS THAT
 YOU ARE USING.
  
 6) NO FIRE SPRINKLER PLANS PROVIDED.
  
 7) A KNOX-BOX WILL BE REQUIRED.
  
 8) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM SYSTEM.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910