| 2003-06-23 00:00:00 | ************ UNSAT *************** |
| | |
| | PLEASE SEE COMMENTS FROM FIRE PLAN |
| | REVIEW FOR POSSIBLE COMENTS THAT WILL |
| | HAVE AN AFFECT ON ELECTRICAL PLANS. |
| | |
| | 1)NOTE: MISSING SMOKE DETECTORS AS REQ`D |
| | INSIDE AND OUTSIDE SLEEPING RMS. |
| | NFPA-72 8-1 |
| | |
| | 2)NOTE: PLEASE SEE SOME RECEPTS MISSING |
| | PER 210-52 |
| | |
| | 3)NOTE: PLEASE SHOW ALL RECEPT SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | ED. 210-8-A6 |
| | |
| | 4)NOTE: PLEASE SEE 210-11C1 FOR A MIN |
| | OF TWO SMALL APPL CIRCUITS REQ`D. |
| | EACH AT 1500VA |
| | |
| | 5)NOTE: PLEASE LIST THE REQ`D ARC FAULT |
| | PROTECTED CIRCUITS. 210-12 |
| | |
| | 6)NOTE:PLEASE SUBMIT AIC RATINGS FOR |
| | MAIN AND SUB MAINS. 110-9/215-5 |
| | |
| | 7)NOTE: PLEASE SEE THAT LIGHTING LOAD |
| | FIGURED FOR UNITS ARE FIGURED TO 3WATTS |
| | PER SQFT, HOWEVER SOME SHOWN ROUNDING |
| | DOWN. ROUNDING UP IS PERMITTED, HOWEVER |
| | ROUNDING DOWN IS NOT. |
| | |
| | 8)NOTE: PLEASE SEE 600-5 FOR MIN SIGN |
| | CIRCUIT REQ`D . |
| | |
| | 9)NOTE: PLEASE SHOW REQ'D SHOW WINDOW |
| | RECEPTS PER 210-62 |
| | |
| | PLEASE SEE ANY COMMENTS FROM OTHER |
| | REVIEWERS THAT HAVE AN AFFECT ON ELECTR- |
| | -ICAL PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |