Notes
Date Text
2003-06-23 00:00:00************ UNSAT ***************
  
 PLEASE SEE COMMENTS FROM FIRE PLAN
 REVIEW FOR POSSIBLE COMENTS THAT WILL
 HAVE AN AFFECT ON ELECTRICAL PLANS.
  
 1)NOTE: MISSING SMOKE DETECTORS AS REQ`D
 INSIDE AND OUTSIDE SLEEPING RMS.
 NFPA-72 8-1
  
 2)NOTE: PLEASE SEE SOME RECEPTS MISSING
 PER 210-52
  
 3)NOTE: PLEASE SHOW ALL RECEPT SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 ED. 210-8-A6
  
 4)NOTE: PLEASE SEE 210-11C1 FOR A MIN
 OF TWO SMALL APPL CIRCUITS REQ`D.
 EACH AT 1500VA
  
 5)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTED CIRCUITS. 210-12
  
 6)NOTE:PLEASE SUBMIT AIC RATINGS FOR
 MAIN AND SUB MAINS. 110-9/215-5
  
 7)NOTE: PLEASE SEE THAT LIGHTING LOAD
 FIGURED FOR UNITS ARE FIGURED TO 3WATTS
 PER SQFT, HOWEVER SOME SHOWN ROUNDING
 DOWN. ROUNDING UP IS PERMITTED, HOWEVER
 ROUNDING DOWN IS NOT.
  
 8)NOTE: PLEASE SEE 600-5 FOR MIN SIGN
 CIRCUIT REQ`D .
  
 9)NOTE: PLEASE SHOW REQ'D SHOW WINDOW
 RECEPTS PER 210-62
  
 PLEASE SEE ANY COMMENTS FROM OTHER
 REVIEWERS THAT HAVE AN AFFECT ON ELECTR-
 -ICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]