Plan Review Notes
Plan Review Notes For Permit 03060274
Permit Number 03060274
Review Stop B
Sequence Number 1
Notes
Date Text
2003-07-08 00:00:001 PLEASE PROVIDE A RECENT PROPERTY
 SURVEY TO DETERMINE LOCATION OF
 ADDITION AND ALTERATIONS.
  
 2THE ADDITION IS SUBJECT TO IMPACT
 FEES COLLECTED BY THE COUNTY.THE
 PERMIT PLANS MUST BE STAMPED BY THAT
 OFFICE AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 CALL 561-233-5025 FOR MORE INFORMATION.
  
 3THE PERMIT PLANS MUST HAVE THE FIRE
 SPRINKLER DESIGN INFORMATION ON THEM.
 SEE FBC 104.3.1.1.
  
 4THE EAST AND WEST SIDES OF THIS
 BUILDING ARE ZERO LOT LINE SETBACK AND
 FBC TABLE 600 DOES NOT ALLOW ANY
 OPENINGS.PLEASE REVISE AS NECESSARY.
  
 5THE SOUTH SIDE, (ALLEY), PROPERTY
 LINE IS MEASURED FROM THE CENTER OF THE
 ALLEY.PLEASE REVISE THAT ELEVATION TO
 BE IN ACCORDANCE WITH FBC TABLE 600 AND
 FBC 705.1.
  
 6THE FRONT AND PROPOSED REAR DOORS
 APPEAR TO SWING OVER THE PUBLIC RIGHT
 OF WAY.SEE FBC 3203.
  
 7SHOW THE METHOD OF COMPLIANCE FOR
 FBC 1803.2 FOR THE FOUNDATION WORK IN
 THE PROXIMITY OF THE ADJACENT BUILDINGS.
  
 8FBC TABLE 600 REQUIRES A THREE HOUR
 FIRE RATING FOR EXTERIOR BEARING WALLS
 LOCATED 0'-3' FROM A PROPERTY LINE IN
 TYPE V CONSTRUCTION.PLEASE SHOW THE
 FIRE DESIGN NUMBER FOR THESE WALLS TO
 BE CONSTRUCTED AND MODIFIED. SEE FBC
 701.5.1.