Plan Review Notes
Plan Review Notes For Permit 03060241
Permit Number 03060241
Review Stop P
Sequence Number 1
Notes
Date Text
2003-06-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT 1 SHOW CLEAR FLOOR SPACE FOR
 REQUIRED HDCP FIXTURES PER SECTIONS
 11-4.16.2, 11-4.18.3, 11-4.19.3 & 11-4.
 24.5. ALSO SHOW 5' TURNING CIRCLES IN
 TOILET ROOMS. (NOT REQUIRED IN STALLS)
 2) SHT 1 INDICATE HEIGHT FOR URNAL PER
 SECTION 11-4.18.2
 3) SHT 5 SANITARY RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. EXISTIN TOILET
 ROOM, (#117), NOT SHOWN ON RISER DIAG.
 ONLY 3 W/C'S ARE SHOWN IN WOMENS TOILET
 ROOM. ONLY 2 LAVS ARE SHOWN IN WOMENS
 TOILET ROOM. ONLY 1 LAV SHOWN IN MENS
 TOILET ROOM, (#106). TWO TRAPS UPSTREAM
 OF URINALS, ARE THEY FLOOR DRAINS??
 ON STACK WITH NEW SINK AND EXISTING SINK
 THERE IS ANOTHER EXISTING SINK AND AN
 EXISTING LAV THAT ARE NOT SHOWN ON THE
 FLOOR PLAN.ALL 5 LAVS SHALL BE SHOWN
 DOWNSTREAM OF UNINALS.
 2) SUBMIT A WATER RISER DIAGRAM. SHOW
 ALL WATER HAMMER ARRESTORS REQUIRED BY
 SECTION 604.9. LOCATE ARRESTORS NEAR THE
 FIXTURES IN AN "EFFECTIVE RANGE" NOT AT
 THE TOP OF THE DROPS IN THE CEILING.
 PDI-WH 201 AND MANUF. INSTALLATION IN-
 STRUCTIONS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692