| 2003-06-23 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 11 |
| | |
| | 1) SHT 1 SHOW CLEAR FLOOR SPACE FOR |
| | REQUIRED HDCP FIXTURES PER SECTIONS |
| | 11-4.16.2, 11-4.18.3, 11-4.19.3 & 11-4. |
| | 24.5. ALSO SHOW 5' TURNING CIRCLES IN |
| | TOILET ROOMS. (NOT REQUIRED IN STALLS) |
| | 2) SHT 1 INDICATE HEIGHT FOR URNAL PER |
| | SECTION 11-4.18.2 |
| | 3) SHT 5 SANITARY RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN. EXISTIN TOILET |
| | ROOM, (#117), NOT SHOWN ON RISER DIAG. |
| | ONLY 3 W/C'S ARE SHOWN IN WOMENS TOILET |
| | ROOM. ONLY 2 LAVS ARE SHOWN IN WOMENS |
| | TOILET ROOM. ONLY 1 LAV SHOWN IN MENS |
| | TOILET ROOM, (#106). TWO TRAPS UPSTREAM |
| | OF URINALS, ARE THEY FLOOR DRAINS?? |
| | ON STACK WITH NEW SINK AND EXISTING SINK |
| | THERE IS ANOTHER EXISTING SINK AND AN |
| | EXISTING LAV THAT ARE NOT SHOWN ON THE |
| | FLOOR PLAN.ALL 5 LAVS SHALL BE SHOWN |
| | DOWNSTREAM OF UNINALS. |
| | 2) SUBMIT A WATER RISER DIAGRAM. SHOW |
| | ALL WATER HAMMER ARRESTORS REQUIRED BY |
| | SECTION 604.9. LOCATE ARRESTORS NEAR THE |
| | FIXTURES IN AN "EFFECTIVE RANGE" NOT AT |
| | THE TOP OF THE DROPS IN THE CEILING. |
| | PDI-WH 201 AND MANUF. INSTALLATION IN- |
| | STRUCTIONS. |
| | |
| | REVIEW BY KEN STEVENS |