| Plan Review Notes For Permit 03060236 |
| Permit Number |
03060236 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-07-10 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | | | | 1) SHT 7 WOMENTS & MENS RESTROOM ELEVAT- | | | IONS, W/C SHALL BE 18" FROM CENTERLINE | | | OF FIXTURE TO WALL. SHOW ON DETAIL. FIG | | | 28 | | | 2) SHT 7 MENS RESTROOM ELEVATION, URNAL | | | HEIGHT TO COMPLY WITH 11-4.18.2. SHOW ON | | | DETAIL. | | | 3) SHOW CLEAR FLOOR SPACE FOR ALL HDCP | | | FIXTURES. 11-4.16.2, 4.18.3, 4.19.3, AND | | | 4.24.5. | | | 4) MINIMUM FIXTURE TABLE 403.1 AND SHT | | | T PLUMBING FIXTURE CALCULATIONS CALLS | | | FOR A DRINKING FOUNTAIN. NOTE SHOWN. | | | 1 DRINKING FOUNTAIN REQUIRED. ALSO SEE | | | SECTION 410.1 | | | 5) SHT 2-P 3/4" WATER LINE TO CHILLER, | | | RPZ BACKFLOW REQUIRED. | | | 6) RPZ BACKFLOW REQUIRED FOR WATER SERV- | | | ICE TO SPACE. BACKFLOW SHALL BE LOCATED | | | MAXIMUM OF 4' ABOVE FLOOR FOR SERVICE & | | | TESTING. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|