Plan Review Notes
Plan Review Notes For Permit 03060236
Permit Number 03060236
Review Stop P
Sequence Number 1
Notes
Date Text
2003-07-10 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT 7 WOMENTS & MENS RESTROOM ELEVAT-
 IONS, W/C SHALL BE 18" FROM CENTERLINE
 OF FIXTURE TO WALL. SHOW ON DETAIL. FIG
 28
 2) SHT 7 MENS RESTROOM ELEVATION, URNAL
 HEIGHT TO COMPLY WITH 11-4.18.2. SHOW ON
 DETAIL.
 3) SHOW CLEAR FLOOR SPACE FOR ALL HDCP
 FIXTURES. 11-4.16.2, 4.18.3, 4.19.3, AND
 4.24.5.
 4) MINIMUM FIXTURE TABLE 403.1 AND SHT
 T PLUMBING FIXTURE CALCULATIONS CALLS
 FOR A DRINKING FOUNTAIN. NOTE SHOWN.
 1 DRINKING FOUNTAIN REQUIRED. ALSO SEE
 SECTION 410.1
 5) SHT 2-P 3/4" WATER LINE TO CHILLER,
 RPZ BACKFLOW REQUIRED.
 6) RPZ BACKFLOW REQUIRED FOR WATER SERV-
 ICE TO SPACE. BACKFLOW SHALL BE LOCATED
 MAXIMUM OF 4' ABOVE FLOOR FOR SERVICE &
 TESTING.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved