2003-07-07 00:00:00PROVISO:MECHANICAL PERMIT 03061650
  
 1.DUCT SMOKE DETECTOR SHALL BE
 INSTALLEDIN THE SUPPLY DUCT NOT IN
 THE RETURN AS DEPICTED ON PLAN SHEET
 AC-1. 2001 FBC(M) 606.2.1.
  
 2.FAN SHUTDOWN WITH NOTIFICATION
 REQUIRED AT FINAL.2001 FBC(M) 606.4.
  