| Plan Review Notes For Permit 03060236 |
| Permit Number |
03060236 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-06-24 00:00:00 | 1)NOTE: PLEASE ALSO SEE CLEARANCE REQ` | | | MENTS FOR MDP AND TRANSFORMER PER 110-26 | | 2003-06-23 00:00:00 | **************** UNSAT *************** | | | | | | 1)NOTE: PLEASE CLARIFY AND SHOW CONNECT- | | | -ION FOR TRANSFORMERS PER 250-30. | | | | | | 2)NOTE: PLEASE SHOW ALL CONTINOUS LOADS | | | @ 125% MIN. (LIGHTING) 215-3/230-42 ETC. | | | SHOW LOAD CALCS.220-3,220-10,220-13 ETC | | | 3)NOTE: PLEASE SHOW SEE MIN SIZING FOR | | | EQUIPMENT GROUNDING CONDUCTORS FOR 30A | | | OCP. 250-122 SOME SHOWN AS #12`S, AND | | | SHOULD BE #10 MIN. | | | | | | 4)NOTE: PLEASE SEE 200A DISCONNECTS FOR | | | HA AND TVSS. IN ELECTRICAL ROOM DIAGRAM | | | SHOWS 200A DISC'C W/ 200A OCP. HOWEVER | | | ELECTRICAL RISER DIAGRAM SHOWS 200A | | | DISC'S W/ 125A OCP? PLEASE CORRELATE. | | | | | | PLEASE SEE COMMENTS FROM OTHER REVIEWERS | | | THAT MAY HAVE AN AFFECT ON ELECTRICAL | | | PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|