Plan Review Notes
Plan Review Notes For Permit 03060236
Permit Number 03060236
Review Stop E
Sequence Number 1
Notes
Date Text
2003-06-24 00:00:001)NOTE: PLEASE ALSO SEE CLEARANCE REQ`
 MENTS FOR MDP AND TRANSFORMER PER 110-26
2003-06-23 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE CLARIFY AND SHOW CONNECT-
 -ION FOR TRANSFORMERS PER 250-30.
  
 2)NOTE: PLEASE SHOW ALL CONTINOUS LOADS
 @ 125% MIN. (LIGHTING) 215-3/230-42 ETC.
 SHOW LOAD CALCS.220-3,220-10,220-13 ETC
 3)NOTE: PLEASE SHOW SEE MIN SIZING FOR
 EQUIPMENT GROUNDING CONDUCTORS FOR 30A
 OCP. 250-122 SOME SHOWN AS #12`S, AND
 SHOULD BE #10 MIN.
  
 4)NOTE: PLEASE SEE 200A DISCONNECTS FOR
 HA AND TVSS. IN ELECTRICAL ROOM DIAGRAM
 SHOWS 200A DISC'C W/ 200A OCP. HOWEVER
 ELECTRICAL RISER DIAGRAM SHOWS 200A
 DISC'S W/ 125A OCP? PLEASE CORRELATE.
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 THAT MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]