| 2003-06-05 00:00:00 | BUILDING DENIED |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) SUBMIT PAID RECEIPT FOR COUNTY IMPACT |
| | FEES. |
| | |
| | 3) SUBMIT A SOIL BORING TEST REPORT AS |
| | REQUIRED BY FBC 1804.2.2. |
| | |
| | 4) SUBMIT A SURVEY. |
| | |
| | 5) REVISE/CLARIFY NOTE #1 ON SHEET A-4. |
| | HANDRAIL AND GUARDRAIL ARE NOT THE SAME. |
| | SEE FBC 1007.5.1 FOR HANDRAIL HEIGHT. |
| | |
| | 6) REVISE STUCCO NOTES ON A5. SPECIFY |
| | THE FASTENER SIZE IN NOTE 3. INDICATE IN |
| | NOTE 7 THAT 3/8" METAL LATH IS REQUIRED |
| | TO BE FASTENED AT EVERY RIB (4"O.C.). |
| | NOTES 4 AND 5 ARE THE SAME. |
| | |
| | 7) REVISE THE GARAGE WALL SECTION ON A4. |
| | UPDATE THE STUD TO PLATE CONNECTORS TO |
| | TO "USP" SPT6 OR SPTH6 FOR 2X6 WALLS. |
| | SEE 2003 USP CATALOG FOR NAILING REQUIRE |
| | MENTS. REVISE THE UPLIFT CAPACITY OF THE |
| | HDPT2 CONNECTOR. SPECIFY CONNECTORS FOR |
| | ATTACHING THE TOP OF THE FIRST FLOOR TO |
| | THE FLOOR TRUSSES. |
| | |
| | 8) SPECIFY THE FLOOR TRUSS TO WALL |
| | CONNECTOR ON DETAIL 1 ON S2. |
| | |
| | 9) REVISE DETAIL C ON S2 TO INDICATE A |
| | BUCKET THAT ATTACHES TO THE WALL AT AN |
| | ANGLE AS SHOWN ON THE LOWER ROOF PLAN. |
| | |
| | 10) REVISE DETAIL 4 ON S2 TO MATCH THE |
| | FLOOR PLAN WHICH SHOWS TWO GIRDERS |
| | MEETING AT 90 DEGREE ANGLES. |
| | |
| | 11) SPECIFY THE LENGTH/EMBEDDMENT DEPTH |
| | OF THE 1/2" DIAMETER EXP. ANCHORS AT THE |
| | WOOD FRAME TO CONCRETE WALL DETAIL ON A5 |
| | AND UPDATE THE SEMCO CONNECTORS. SEMCO |
| | WAS PURCHASED BY USP. |
| | |
| | 12) DETAIL E ON S-3 IS INCORRECTLY |
| | SPECIFIED FOR THE TRUSS ABOVE THE MASTER |
| | BEDROOM. THIS WALL IS MASONRY AND NOT |
| | WOOD FRAME. PLEASE CORRECT. |
| | |
| | 13) REVISE THE UPLIFT CAPACITIES FOR THE |
| | TRUSS CONNECTORS TO REFLECT VALUES THAT |
| | DO NOT HAVE STRESS INCREASES FOR THE |
| | STEEL CALCULATIONS. SEE FBC 1609.4.3 AND |
| | AND 2003 USP CATALOG. |
| | |
| | 14) PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - SLIDING GLASS DOORS |
| | - OVERHEAD GARAGE DOOR |
| | - ARCHED TO FIXED GLASS WINDOW |
| | |
| | 15) THE OWNER AND CONTRACTOR INFORMATION |
| | ON THE ENERGY CALCULATIONS DOES NOT |
| | MATCH THE APPLICATION OR CITY RECORDS. |
| | |
| | 16) THE OWNER INFORMATION LISTED ON THE |
| | APPLICATION DOES NOT MATCH THE OWNER OF |
| | RECORD WITH THE CITY OR COUNTY. |
| | |
| | 17) OWNER/AGENT IS REQUIRED TO SIGN THE |
| | ENERGY CALCULATION FORM. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |