| 2003-06-06 00:00:00 | BUILDING DENIED |
| | |
| | 1) SUBMIT RECEIPT FOR IMPACT FEES. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3) SUBMIT SOIL BORING TEST REPORT. |
| | |
| | 4) REVISE/CLARIFY NOTE #1 ON SHEET A4. |
| | HANDRAIL AND GUARDRAIL ARE NOT THE SAME. |
| | SEE FBC 1007.5.1 FOR HANDRAIL HEIGHT. |
| | |
| | 5) THE "USP" TP6X AND TP8X CONNECTORS |
| | SPECIFIED FOR THE STUD PLATE CONNECTION |
| | ON THE WD. FRAME TO CONC. WALL DETAIL ON |
| | A6 ARE NOT LISTED IN THE 2003 USP |
| | CATALOG. ARE THESE "USP" SPT OR SPTH |
| | CONNECTORS? |
| | |
| | 6) SPECIFY THE CONNECTOR FOR THE FLOOR |
| | TRUSS TO THE CONC. WALL ON DETAIL 1/S2. |
| | |
| | 7) SPECIFY THE CONNECTORS FOR EACH END |
| | OF THE FLOOR GIRDER TRUSS SHOWN ON |
| | LOWER ROOF PLAN AT THE CENTER OF THE |
| | STRUCTURE AND SUPPORTED IN THE CENTER BY |
| | THE STEEL COLUMN. |
| | |
| | 8) REVISE THE UPLIFT CAPACITIES OF THE |
| | TRUSS CONNECTORS ON SHEETS S2 AND S3 TO |
| | VALUES THAT DO NOT INCLUDE A ONE-THIRD |
| | INCREASE ON THE STEEL CALCULATIONS. SEE |
| | FBC 1609.4.3 AND 2003 USP CATALOG. |
| | |
| | 9) THE OWNER AND CONTRACTOR INFORMATION |
| | ON THE ENERGY CALCULATIONS AND |
| | APPLICATION DO NOT MATCH THE CITY AND |
| | COUNTY RECORDS. PLEASE CORRECT. |
| | |
| | 10) THE ENERGY CALC. FORM IS REQUIRED TO |
| | BE SIGNED BY THE OWNER/AGENT. |
| | |
| | 11) PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - ARCHED TOP FIXED GLASS WINDOWS |
| | - STRUCTURAL MULLIONS (EXPIRED 5/1/03) |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |