| Plan Review Notes For Permit 03060175 |
| Permit Number |
03060175 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-10-07 00:00:00 | ************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE CORRELATE RISER DIAGRAM, | | | 200A METER/ MAIN FEEDING 150A PANEL? | | | | | | 2)NOTE: PLEASE SEE TABLE 9 FOR FOR | | | CONDUIT SIZING/FILL. | | | | | | 3)NOTE: PLEASE SEE THAT SOME NOTES FROM | | | FIRST REVIEW HAVE NOT BEEN ADDRESSED AND | | | PLEASE SEE COPY OF FS 553.80(2)(B) WITH | | | RESPECT TO DESIGN PROFESSIONALS. | | | | | | 4)NOTE: PLEASE COMPLETE ELECTRICAL LOADS | | | /PANELS/OCP ETC. SOME SHOWN BLANK.215.5 | | | 220 | | | 5)NOTE: PLEASE SEE NOTES 2,3,4,5,7,8 | | | FROM PREVIOUS REVIEW. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected]. | | | | | | | | | PLEASE INCLUDE ALL LICENSE INFORMATION | | | ON TITLE BLOCK AS REQ'D UNDER FS AND FAC | | | 481 AND 61G1-16.004 |
|