Plan Review Notes
Plan Review Notes For Permit 03060175
Permit Number 03060175
Review Stop E
Sequence Number 2
Notes
Date Text
2003-10-07 00:00:00************** UNSAT *****************
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRAM,
 200A METER/ MAIN FEEDING 150A PANEL?
  
 2)NOTE: PLEASE SEE TABLE 9 FOR FOR
 CONDUIT SIZING/FILL.
  
 3)NOTE: PLEASE SEE THAT SOME NOTES FROM
 FIRST REVIEW HAVE NOT BEEN ADDRESSED AND
 PLEASE SEE COPY OF FS 553.80(2)(B) WITH
 RESPECT TO DESIGN PROFESSIONALS.
  
 4)NOTE: PLEASE COMPLETE ELECTRICAL LOADS
 /PANELS/OCP ETC. SOME SHOWN BLANK.215.5
 220
 5)NOTE: PLEASE SEE NOTES 2,3,4,5,7,8
 FROM PREVIOUS REVIEW.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected].
  
  
 PLEASE INCLUDE ALL LICENSE INFORMATION
 ON TITLE BLOCK AS REQ'D UNDER FS AND FAC
 481 AND 61G1-16.004