| 2003-10-20 00:00:00 | *****CORRECTIONS***** |
| | |
| | SAMANTHA THYNG, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE |
| | A PERMIT CAN BE ISSUED. |
| | |
| | 2.)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE PLANS MUST BE |
| | STAMPED AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION.233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 3.)THE SURVEY PROVIDED IS DIFFICULT TO |
| | READ, BUT IT APPEARS THAT THE EXISTING |
| | HOUSE IS AT 4.7' FROM THE PROPERTY LINE. |
| | THE SITE PLAN PREPARED BY THE ARCHITECT |
| | SHOWS THE HOUSE AT 5'.PLEASE ADDRESS. |
| | |
| | 4.)SEE PREVIOUS CORRECTION LIST #9; |
| | IMPACT PROECTION REQUIRED FBC1601. |
| | PROVIDE TWO COPIES OF PRODUCT APPROVALS |
| | AND A HURRICANE SHUTTER INSTALLATION |
| | SCHEDULE, SEE ATTACHED.IF THIS IS NOT |
| | SUBMITTED BEFORE THE ISSUANCE OF THE |
| | PERMIT, A SEPARATE PERMIT FOR THIS ITEM |
| | WILL BE REQUIRED. |
| | |
| | 5.)PREVIOUS CORRECTION LIST, ITEM #4, |
| | REQUESTED COMPLIANCE WITH FBC3401.7.1.2 |
| | INCLUDING BEDROOM EMERGENCY EGRESS AND |
| | SMOKE DETECTORS.THIS APPLIES TO THE |
| | EXISTING HOUSE.SHOW COMPLIANCE, EITHER |
| | WITH AN EXISTING FLOOR PLAN OR A |
| | LETTER WITH A WINDOW SCHEDULE (1 PER |
| | EXISTING BEDROOM), STATING TYPE OF |
| | WINDOW AND SIZE. |
| | |
| | 6.)SEE PREVIOUS CORRECTION LIST, ITEM |
| | #10.TWO COPIES OF ALL DOCUMENTATION IS |
| | REQUIRED, INCLUDING ALL PRODUCT |
| | APPROVALS AND ENERGY CALCS.ANY PRODUCT |
| | APPROVALS NOT SUBMITTED FOR REVIEW WILL |
| | REQUIRE A SEPARATE PERMIT (MULLIONS, |
| | IMPACT PROTECTION, SLIDING GLASS DOOR, |
| | ROOF). |
| | |
| | 7.)ITEM 13, NOT ADDRESSED.DOES NOT |
| | SHOW FIREBLOCKING FBC2305.1.4. |
| | |
| | 8.)STAIRS TO COMPLY WITH FBC1007.3(1), |
| | SUM OF TWO RISERS AND A TREAD TO BE AT |
| | LEAST 24". |
| | |
| | 9.)PROVIDE A GUARDRAIL DETAIL. |
| | |
| | 10.) HANDRAIL AND GUARDRAIL TO COMPLY |
| | WITH FBC1608.2. |
| | |
| | 11.) A-1, CONNECTOR SCHEDULE, UPLIFT FOR |
| | CONNECTORS EXCEED MAXIMUM ALLOWED IN THE |
| | CATALOG. |
| | |
| | 12.) TO EXPEDITE PLAN REVIEW, CLOUD ALL |
| | CHANGES (SOME CHANGES WERE CLOUDED, SOME |
| | WERE NOT). |
| | |
| | 13.) SIGN THE OWNER/AGENT LINE OF THE |
| | ENERGY CALC FBC13-101.2.PROVIDE TWO |
| | COPIES. |