| Plan Review Notes For Permit 03060175 |
| Permit Number |
03060175 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-06-10 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) SHT A-2 SANITARY RISER DIAGRAM DOES | | | NOT MEET CODE REQUIREMENTS. TUB & SHOWER | | | NOT VENTED PROPERLY. (TABLE 906.1) | | | ISLAND VENT OR AIR ADMITTENCE VALVE REQ- | | | UIRED FOR SALAD SINK. TUB & SHOWER SHALL | | | NOT DRAIN INTO A HORIZONTAL TEE. (TABLE | | | 706.3). LAVS SHALL NOT BE DRAINED TO A | | | CROSS FITTING. (THEY ARE NOT BACK TO | | | BACK). SEE RED LINE CHANGES ON PLANS. | | | PLEASE MAKE CORRECTIONS AND RESUBMIT | | | PLANS FOR REVIEW. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|