| Plan Review Notes For Permit 03060175 |
| Permit Number |
03060175 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-06-10 00:00:00 | ************** UNSAT *************** | | | | | | 1)NOTE: PLEASE SEE MISSING KITCHEN | | | ISLAND RECEPTS PER 210-52C-2 & C-5. | | | | | | 2)NOTE: PLEASE SHOW ALL OUTLETS SERVING | | | KITCHEN COUNTERSPACE AS GFI/ GFI PROTECT | | | -ED. 210-8-A-6 | | | | | | 3)NOTE: PLEASE LIST THE REQ`D ARC FAULT | | | PROTECTED CIRCUIT(S) PER 210-12 | | | | | | 4)NOTE: PLEASE OCP FOR AHU`S, SHOWN ON | | | PANEL SCHEDULE AS 2-POLE 50'S AND SHOWN | | | ON LOAD CALCS AS 5KW?MAX OCP 150% | | | | | | 5)NOTE: PLEASE CLARIFY 50A OCP SHOWN AS | | | TRIP FOR DISH/DISP.? ALSO SHOWS 20A? | | | | | | 6)NOTE: PLEASE MOVE GFI IN BATH TO | | | MEET 210-52D 3' FROM LAV EDGE. | | | | | | 7)NOTE; PLEASE SUBMIT AIC RATINGS FOR | | | NEW EQUIPMENT BEING INSTALLED FOR | | | SERVICE.110-9/215-5 | | | | | | 8)NOTE: PLEASE SEE MISSING SD`S IN/OUT | | | BEDROOMS AND ON EACH LEVEL OF MULTI- | | | -LEVEL. NFPA-72 8-1.4.2 | | | | | | 9)NOTE: PLEASE CLARIFY GROUNDING/BONDING | | | SIZE OF CONDUCTOR TO COLD WATER PIPE? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW.IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|