2003-06-17 00:00:00********CORRECTIONS*******
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)A NOTICE OF COMMENCEMENT IS
 REQUIRED TO BE FILED WITH THE CLERK OF
 COURTS BEFORE A PERMIT CAN BE ISSUED.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE ORIGINAL RECEIPT ATTACHED TO THE
 APPLICATION.233-5025
  
 3.)PROVIDE A SURVEY FOR THIS PROPERTY.
  
 4.)AREA CALCULATIONS SHOULD INCLUDE
 THE EXISTING, PROPOSED, AND NEW TOTAL.
 ADDITIONS OF OVER 25% MUST COMPLY WITH
 FBC 3401.7.1.2.SHOW COMPLIANCE ON
 EXISTING HOUSE IF THE ADDITION IS OVER
 25%; BEDROOM EGRESS, ACCESSIBLE
 BATHROOM, POOL SAFETY, SMOKE DETECTORS.
  
 5.)SPECIFY SPACING, 1-A1.
  
 6.)ENERGY CALCS REQUIRED, FBC13-101.2.
  
 7.)SMOKE DETECTORS REQUIRED,FBC905.2.2
  
 8.)ATTIC ACCESS REQUIRED, FBC2309.6.
  
 9.)IMPACT PROTECTION REQUIRED FBC
 1601.IF SHUTTERS ARE USED, SUBMIT A
 HURRICANE SHUTTER ATTACHMENT SCHEDULE,
 SEE ATTACHED.
  
 10.) SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR THE WINDOWS, IMPACT
 PROTECTION, MULLIONS, SLIDING GLASS
 DOOR, ROOF COVERING.IF PRODUCT
 APPROVALS ARE NOT SUBMITTED, A SEPARATE
 PERMIT FOR THOSE ITEMS WILL BE REQUIRED.
  
 11.)PROVIDE A GUARDRAIL DETAIL.
  
 12.)PROVIDE A STAIR RAILING AND
 HAND RAIL DETAIL.
  
 13.)PROVIDE A STRUCTURAL DETAIL FOR
 THE STAIRS, INCLUDING FIREBLOCKING.
  
 14.)THE DOOR BUCK (A2) MUST COMPLY
 WITH FBC 1707.4.4.2.
  
 15.)THE POOL MUST COMPLY WITH THE
 RESIDENTIAL SWIMMING POOL SAFETY ACT
 FS 515.
  
 16.)DRAFTSTOPPING REQUIRED, FBC 705.3.
 PROVIDE A DRAFTSTOP DETAIL AND SHOW
 LOCATIONS ON THE JOIST FRAMING PLAN A1.
  
 17.)SPECIFY SOFFIT VENTING TO COMPLY
 WITH FBC 2309.7.
  
 18.)GABLES ARE TO BE STRUCTURALLY
 CONTINUOUS, FBC 1918.3.1.