| Plan Review Notes For Permit 03060166 |
| Permit Number |
03060166 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-07-25 00:00:00 | DENIED | | | REFERENCE: FBC-2001 FUEL GAS | | | | | | 1) TABLES SUBMITTED WITH PLANS ARE NOT | | | APPROVED. | | | 2) PLEASE INDICATE MANUFACTURE OF PE | | | PIPE AND SUBMIT MANUF SHEETS. MANUF. | | | INFORMATION REQUIRED FOR SIZING, CHART | | | FROM MANUFACTURE REQUIRED. | | | 3) DISTANCE FROM METER AND SIZE OF PIPE | | | SHOW THAT A 1/2 POUND SYSTEM WILL BE | | | INSUFFICIENT. EITHER 2" PIPE WILL BE RE- | | | QUIRED OR INCREASE DELIVERY PRESSURE TO | | | A 2 LB SYSTEM WITH REGULATORS. | | | 4) CUT SHEET WILL BE REQUIRED FOR REG- | | | ULATORS IF 2 LB SYSTEM IS USED. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|