| Plan Review Notes For Permit 03060138 |
| Permit Number |
03060138 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-07-08 00:00:00 | CHECKLIST: | | | 1-SURVEY DOESN'T MATCH MODEL 203 AS | | | SHOWN ON PLANS. IT WAS MODEL 204 AND | | | IT WAS CROSS OUT TO READ MODEL 203. | | | REVISE AS REQUIRED. CLARIFY WHICH | | | MODEL IS GOING TO BE BUILT. | | | 2-PROVIDE COMPLETE & CORRECT INFORMATION | | | FOR STORM SHUTTERS, INCLUDING CORRECT | | | ANCHOR SPACING FOR WOOD ANCHORS OR | | | APPLY FOR A SEPARATE PERMIT. | | | 3-REVISE FRONT ELEVATION TO MATCH TYPE | | | OF WINDOW SPECIFIED ON THE WINDOW | | | SCHEDULE. | | | 4-REVISE TRUSS ANCHOR SCHEDULE AND ALL | | | DETAILS THAT ARE AFFECTED BY SECTION | | | 1609.4.3 FBC 2001, WHICH DOES NOT | | | PERMIT THE ALLOWABLE STEEL STRESS TO | | | BE INCREASED. |
|