Plan Review Notes
Plan Review Notes For Permit 03060118
Permit Number 03060118
Review Stop M
Sequence Number 1
Notes
Date Text
2003-06-04 00:00:00CALLED MR. TIM FRANK, PERMIT APPLICATION
 INDICATES ADDITION IS 11,000 SQ FT.
 ENERGY MANUAL J CALCS WERE NOT PROVIDED
 AS REQUESTED FROM H. MOSER ON 1ST REVIEW
 RETURN AIR REQUIRED FROM MASTER BEDROOM
 AREA.RETURN AIR NOT INDICATED ON PLAN
 AT ANY LOCATION.