| Plan Review Notes For Permit 03060103 |
| Permit Number |
03060103 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-06-06 00:00:00 | PLEASE NOTE THE FOLLOWING INFORMATION: | | | | | | 1.RETURN OR TRANSFER AIR REQUIRED FROM | | | BEDROOM AREAS.2001 FBC(M) 601.4 | | | | | | 2.A MINIMUM OF 4" CLEARANCE AROUND | | | AHU IS REQUIRED. 2001 FBC(M) 603.1.3 | | | | | | 3.EXHAUST FAN REQUIRED FROM BATHROOM | | | AREAS.2001 FBC(M) 402.3.1 | | | | | | 4.CONDENSATE SHALL TERMINATE A MINIMUM | | | OF 12" AWAY FROM THE BUILDING STRUCTURE. | | | 2001 FBC 1503.4.4 |
|