| 2003-11-20 00:00:00 | *****CORRECTIONS****** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 |
| | |
| | 1.)SEPARATE PERMITS REQUIRED. |
| | |
| | 2.)THE NOTICE OF COMMENCEMENT |
| | SUBMITTED WAS FOR 1017 SELKIRK (WRONG |
| | ADDRESS). |
| | |
| | 3.)SEE PREVIOUS LIST, ITEM #4.THE |
| | INSULATION CANNOT BE R4.0 WHEN THE |
| | ENERGY CALC SPECIFIES A MINIMUM OF R4.2. |
| | |
| | 4.)SEE PREVIOUS LIST, ITEM #9, SHEET |
| | 2 STILL REFERS TO "UNLOAD DESIGN". |
| | |
| | 5.)SEE PREVIOUS LIST, ITEM #12, |
| | CONNECTOR SCHEDULE HAS AN UPLIFT FOR |
| | TWO STRAPS THAT IS LESS THAN THE UPLIFT |
| | ON THE PLAN FOR THAT CONNECTOR.REVISE |
| | THE CONNECTOR SCHEDULE UPLIFT. |
| | |
| | 6.)SEE PREVIOUS LIST, ITEM #13, |
| | PROVIDE A WINDOW & DOOR BUCK ATTACHMENT |
| | DETAIL. |
| | |
| | 7.)SEE PREVIOUS LIST, ITEM #16, |
| | PROVIDE TWO COPIES OF THE WINDOW |
| | MULLION PRODUCT APPROVAL. |
| | |
| | 8.)ADDITIONAL FEES DUE, $364.43 |
| | (RADON AND VALUE ADJUSTMENT), SEE |
| | ATTACHED BZ233275. |
| | |
| | 9.)SEE PREVIOUS LIST.WHEN |
| | RESUBMITTING, ALL CHANGES MUST BE |
| | CLEARLY MARKED WITH CLOUDS OR TRIANGLES. |
| | |
| | 10.) THE CHANGES TO A SEALED PLAN MUST |
| | BE INITIALED BY THE ENGINEER. |
| | |
| | 11.)THE ENGINEER'S LICENSE NUMBER |
| | IS REQUIRED TO BE ON EACH SHEET, FAC |
| | 61G15-23.002. |
| | |
| | 12.)SEE ATTACHED NOTICE REGARDING |
| | FS553.80(2)(B). |
| | |
| | 13.)PROVIDE A KEY PLAN AND HURRICANE |
| | SHUTTER INSTALLATION SCHEDULE (SEE |
| | ATTACHED). |
| | |
| | 14.)IDENTIFY THE JOB ON THE TITLE |
| | BLOCK (ADDRESS OR LOT NUMBER). |
| | |
| | 15.)THERE IS AN "EXTENDED WALL". |
| | PROVIDE A DETAIL.A WALL IS NOT |
| | "DECORATION PURPOSE ONLY", A WALL IS |
| | ALWAYS A STRUCTURAL ELEMENT.SHOW ON |
| | THE FOUNDATION PLAN. |