| Plan Review Notes For Permit 03060080 |
| Permit Number |
03060080 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-11-03 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) REVISIONS TO A SIGNED, SEALED, AND | | | DATED PLANS SHALL BE SIGNED, SEALED, AND | | | DATED BY THE ENGINEER OF RECORD. SECTION | | | 104.2.2 | | | 2) SHOW ALL PIPE SIZES ON REVISION. | | | SECTION 104.2.1 | | | 3) REMOVE ALL EXCESS PIPING FROM THE | | | RISER DIAGRAM. (SEE RED LINE AREAS) | | | SECTION 104.2.1 | | | 4) CLEANOUT AT WASH MACHINE SHALL BE | | | LOCATED 4' ABOVE THE FLOOR FOR ACCESS. | | | SECTION 708.10 | | | | | | (SEE RED LINES AND CIRCLES ON SANT. | | | RISER DIAGRAM SHOWING CORRECTIONS TO BE | | | MADE. CORRECT - SIGN/SEAL/DATE | | | REVISION, | | | AND MAKE SURE TITLE BLOCK WITH ALL | | | REQUIRED INFORMATION IS ON REVISION) | | | | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|