Plan Review Notes
Plan Review Notes For Permit 03060080
Permit Number 03060080
Review Stop P
Sequence Number 3
Notes
Date Text
2004-11-03 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) REVISIONS TO A SIGNED, SEALED, AND
 DATED PLANS SHALL BE SIGNED, SEALED, AND
 DATED BY THE ENGINEER OF RECORD. SECTION
 104.2.2
 2) SHOW ALL PIPE SIZES ON REVISION.
 SECTION 104.2.1
 3) REMOVE ALL EXCESS PIPING FROM THE
 RISER DIAGRAM. (SEE RED LINE AREAS)
 SECTION 104.2.1
 4) CLEANOUT AT WASH MACHINE SHALL BE
 LOCATED 4' ABOVE THE FLOOR FOR ACCESS.
 SECTION 708.10
  
 (SEE RED LINES AND CIRCLES ON SANT.
 RISER DIAGRAM SHOWING CORRECTIONS TO BE
 MADE. CORRECT - SIGN/SEAL/DATE
 REVISION,
 AND MAKE SURE TITLE BLOCK WITH ALL
 REQUIRED INFORMATION IS ON REVISION)
  
  
  