| Notes |
| Date |
Text |
| 2003-11-12 00:00:00 | DENIED | | | ~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | THESE COMMENTS WERE NOT ADDRESSED ON | | | THE PLAN.PLEASE CORRECT AND RESUBMIT | | | FORREVIEW. | | | | | | 1} PLEASE INDICATE THE SIZE OF THE | | | SERVICE CONDUCTORS IN THE RISER(FROM | | | WEATHERHEAD TO METER). | | | | | | 2} THE PANEL SCHEDULE ONLY SHOWS ONE AHU | | | AND THERE ARE TWO SHOWN ON THE PLAN | | | (SEE MECH PLAN).PLEASE REVISE THE LOAD | | | CALCULATION AS WELL. | | | | | | 3} PLEASE SHOW ALL OUTLET SPACING | | | TO MEET 2',6',12' RULE PER 210-52.SEE | | | REVIEWED SET OF PLANS IF YOU HAVE | | | QUESTIONS REGARDING THIS ARTICLE. | | | | | | THESE COMMENTS ARE NEW: | | | | | | SHOW LOCATION OF THE SERVICE EQUIPMENT | | | ON THE PLAN. SHOW COMPLIANCE WITH | | | 230.70 CWPB AMMENDMENTS. | | | | | | COMPLY WITH 210.52(C)(1) IN THE KITCHEN. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|