2003-11-19 00:00:00******CORRECTIONS*****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)SEPARATE PERMITS REQUIRED.
  
 2.)SEE PREVIOUS LIST, ITEM #4.YOU
 CANNOT SPECIFY R4 OR R4.2 WHEN THE
 ENERGY CALCS REQUIRE A MINIMUM OF 4.2.
  
 3.)SEE PREVIOUS LIST, ITEM #9, NOT
 ADDRESSED.SHEET 2 REFERS TO "BUILDING
 UNLOAD CERTIFICATION", REVISE.
  
 4.)SEE PREVIOUS LIST, ITEM #12.THE
 CONNECTOR SCHEDULE, SHEET 2, SPECIFIES
 TWO STRAPS BUT UPLIFT SHOWS THE SAME
 AS ONE.ON THE FRAMING PLAN, CONNECTOR
 TWO IS SPECIFIED WITH AN UPLIFT WHICH
 EXCEEDS THE TABLE.REVISE THE UPLIFT.
  
 5.)SEE PREVIOUS LIST, ITEM #13.
 PROVIDE A WINDOW AND DOOR BUCK
 ATTACHMENT DETAIL.
  
 6.)SEE PREVIOUS LIST, ITEM #16.
 PROVIDE TWO COPIES OF THE WINDOW
 MULLION PRODUCT APPROVAL.THE FLOOR
 PLAN SHOWS THE WINDOW OPENING AS A
 SINGLE, SCHEDULE SHOWS AS A "PAIR".
  
 7.)THE DOOR PRODUCT APPROVALS ARE
 MISSING THE TECHNICAL SHEETS.
  
 8.)ADDITIONAL FEES DUE, $364.43
 (VALUE ADJUSTMENT AND RADON), SEE
 ATTACHED BZ233274.
  
 9.)SEE PREVIOUS LIST.ALL CHANGES
 TO THE PLAN ARE TO BE CLEARLY MARKED
 WITH CLOUDS OR TRIANGLES.
  
 10.) THERE IS AN "EXTENDED WALL" ON THE
 ELEVATION.PROVIDE A DETAIL AND SHOW
 THE WALL ON THE FOUNDATION PLAN.
  
 11.) CHANGES MADE TO A SEALED PLAN ARE
 TO BE INITIALED BY THE ENGINEER.
  
 12.) SUBMIT A SECOND COPY OF THE SOILS
 REPORT.
  
 13.) THE APPROVED ZONING SURVEY IS
 MISSING FROM THE PACKAGE.SUBMIT, IF
 AVAILABLE.
  
 14.)IDENTIFY THE JOB ON THE TITLE
 BLOCK BY EITHER ADDRESS OR LOT NUMBER.
  
 15.)SEE ATTACHED NOTICE IN REGARDS
 TO FS553.80(2)(B).
  
 16.)PROVIDE A KEY PLAN AND A HURRICANE
 SHUTTER INSTALLATION SCHEDULE.