| 2003-11-19 00:00:00 | ******CORRECTIONS***** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 |
| | |
| | 1.)SEPARATE PERMITS REQUIRED. |
| | |
| | 2.)SEE PREVIOUS LIST, ITEM #4.YOU |
| | CANNOT SPECIFY R4 OR R4.2 WHEN THE |
| | ENERGY CALCS REQUIRE A MINIMUM OF 4.2. |
| | |
| | 3.)SEE PREVIOUS LIST, ITEM #9, NOT |
| | ADDRESSED.SHEET 2 REFERS TO "BUILDING |
| | UNLOAD CERTIFICATION", REVISE. |
| | |
| | 4.)SEE PREVIOUS LIST, ITEM #12.THE |
| | CONNECTOR SCHEDULE, SHEET 2, SPECIFIES |
| | TWO STRAPS BUT UPLIFT SHOWS THE SAME |
| | AS ONE.ON THE FRAMING PLAN, CONNECTOR |
| | TWO IS SPECIFIED WITH AN UPLIFT WHICH |
| | EXCEEDS THE TABLE.REVISE THE UPLIFT. |
| | |
| | 5.)SEE PREVIOUS LIST, ITEM #13. |
| | PROVIDE A WINDOW AND DOOR BUCK |
| | ATTACHMENT DETAIL. |
| | |
| | 6.)SEE PREVIOUS LIST, ITEM #16. |
| | PROVIDE TWO COPIES OF THE WINDOW |
| | MULLION PRODUCT APPROVAL.THE FLOOR |
| | PLAN SHOWS THE WINDOW OPENING AS A |
| | SINGLE, SCHEDULE SHOWS AS A "PAIR". |
| | |
| | 7.)THE DOOR PRODUCT APPROVALS ARE |
| | MISSING THE TECHNICAL SHEETS. |
| | |
| | 8.)ADDITIONAL FEES DUE, $364.43 |
| | (VALUE ADJUSTMENT AND RADON), SEE |
| | ATTACHED BZ233274. |
| | |
| | 9.)SEE PREVIOUS LIST.ALL CHANGES |
| | TO THE PLAN ARE TO BE CLEARLY MARKED |
| | WITH CLOUDS OR TRIANGLES. |
| | |
| | 10.) THERE IS AN "EXTENDED WALL" ON THE |
| | ELEVATION.PROVIDE A DETAIL AND SHOW |
| | THE WALL ON THE FOUNDATION PLAN. |
| | |
| | 11.) CHANGES MADE TO A SEALED PLAN ARE |
| | TO BE INITIALED BY THE ENGINEER. |
| | |
| | 12.) SUBMIT A SECOND COPY OF THE SOILS |
| | REPORT. |
| | |
| | 13.) THE APPROVED ZONING SURVEY IS |
| | MISSING FROM THE PACKAGE.SUBMIT, IF |
| | AVAILABLE. |
| | |
| | 14.)IDENTIFY THE JOB ON THE TITLE |
| | BLOCK BY EITHER ADDRESS OR LOT NUMBER. |
| | |
| | 15.)SEE ATTACHED NOTICE IN REGARDS |
| | TO FS553.80(2)(B). |
| | |
| | 16.)PROVIDE A KEY PLAN AND A HURRICANE |
| | SHUTTER INSTALLATION SCHEDULE. |