Plan Review Notes For Permit 03060080
Permit Number 03060080
Review Stop E
Sequence Number 1
Notes
Date Text
2003-06-23 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE NECESSARY CHANGES TO
 PLANS AND RESUBMIT FOR REVIEW.
  
 1} PLEASE INDICATE THE SIZE OF THE
 SERVICE CONDUCTORS IN THE RISER.
  
 2} THE PANEL SCHEDULE ONLY SHOWS ONE
 AHU AND THERE ARE TWO SHOWN ON THE PLAN
 PLEASE REVISE THE LOAD CALCULATION AS
 WELL.
  
 3} THE AHU IS LISTED AT 7KW ON THE
 SCHEDULE AND 5KW ON THE MECHANICAL
 PLAN,PLEASE CORRELATE.
  
 4} PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.SEE
 REVIEWED SET OF PLANS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW