| Plan Review Notes For Permit 03060080 |
| Permit Number |
03060080 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-06-23 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION,MAKE NECESSARY CHANGES TO | | | PLANS AND RESUBMIT FOR REVIEW. | | | | | | 1} PLEASE INDICATE THE SIZE OF THE | | | SERVICE CONDUCTORS IN THE RISER. | | | | | | 2} THE PANEL SCHEDULE ONLY SHOWS ONE | | | AHU AND THERE ARE TWO SHOWN ON THE PLAN | | | PLEASE REVISE THE LOAD CALCULATION AS | | | WELL. | | | | | | 3} THE AHU IS LISTED AT 7KW ON THE | | | SCHEDULE AND 5KW ON THE MECHANICAL | | | PLAN,PLEASE CORRELATE. | | | | | | 4} PLEASE SHOW ALL OUTLET SPACING | | | TO MEET 2`,6`,12` RULE PER 210-52.SEE | | | REVIEWED SET OF PLANS. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|