| Plan Review Notes For Permit 03060041 |
| Permit Number |
03060041 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-06-26 00:00:00 | PLAN DENIED | | | 1) HYDRONIC PIPING SYSTEMS SHALL BE | | | TESTED HYDRONICALLY AT ONE-HALF TIMES | | | THE MAXIMUM SYSTEM DESIGN PRESSURE, | | | BUT NOT LESS THAN 100 PSI.FROM RISER | | | TO A/C #1&2 | | | 2) HAVE PIPE DIAGRAM WITH PLANS WITH | | | PLANS | | | 3) HAVE EQUIPMENT SPECIFICATION WITH | | | PLANS | | | PLAN REVIEW BY HAROLD MOSER | | | (561)805-6732 |
|