| Plan Review Notes For Permit 03060017 |
| Permit Number |
03060017 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-06-18 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 03060017 | | | ADD: 92 ARLINGTON PLACE | | | CONT: ACTION HURRICANE SHUTTERS | | | TEL: (561)262-9591 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | ACTION: DENIED | | | | | | 1) MISSING ORIGINAL PERMIT APPLICATION, | | | SUBMIT ORIGINAL OR SIGN DUPLICATE. | | | | | | 2) PROVIDE COPY OF SIGNED CONTRACT | | | INDICATING VALUE. | | | | | | 3) INSTALLATION SCHEDULE, TYPE OF CONSTR | | | UCTION, APPLICANT WROTE "CONCRETE" AND | | | TOOK THE VALUES FOR CONCRETE FROM TABLES | | | DISCREPANCY, WHERE CONTRACTOR TOOK THE | | | VALUES FOR CONCRETE @ 12" O.C., WHEN YOU | | | LOOK AT THE BUILDING PLANS THE TYPE OF | | | CONSTRUCTION IS FILLED CELL MASONARY, | | | NOT CONCRETE. | | | | | | THE INSTALLATION SCHEDULE PROVIDED DOES | | | NOT PROVIDE THE INFORMATION THE CITY | | | REQUIRES, SUCH AS OPENING SIZE, SHUTTER | | | SIZE, WIDTH & HEIGHT, IF THE SHUTTER | | | SPANS ARE VERT/ HORZ. IF STORM BARS ARE | | | REQUIRED? ANCHOR SPACING FOR TOP/ BOTTOM | | | AND TYPE OF ANCHOR FOR EACH, IF THE | | | STORM PANELS REQUIRE BOLTS? | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 805-6715 |
|