2003-06-09 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
 FBC-2001 CHAPTER 13
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) COMPLY WITH FBC-2001 SEC 424.2
 PRIVATE SWIMMING POOLS.(ADD TO NOTES)
 2) FBC-2001 SEC 424.2.6.1 ENGINEERING
 DESIGN, CONSTRUCTION AND WORKMANSHIP.
 ANSI/NSPI-4 92, AND NSPI-5. (ADD TO
 NOTES)
 3) FBC-2001424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL OR ADD NOTE)(SUBMITTAL)
 4) PIPING SCHEMATIC DOES NOT REFLECT THE
 POOL LAYOUT. SCHEMATIC INDICATES DUAL
 MAIN DRAINS FOR SPA, BUT POOL LAYOUT
 SHOWS 4 MAIN DRAINS IN POOL. SCHEMATIC
 DOES NOT SHOW VACUUM LINE INDICATED ON
 THE POOL LAYOUT. PLEASE CLAIRFY. PLEASE
 SUBMIT NEW SHEETS FOR REVIEW.
 5) A PROFESSIONAL ENGINEER SHALL SIGN
 HIS NAME AND AFFIX HIS SEAL TO ALL PLANS
 SPECIFICATIONS, REPORTS OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSONAL
 ENGINEER. 61G15-23.002
 6) ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME, ADDRESS AND NUMBER ON EACH
 SHEET.
  