| 2004-03-03 00:00:00 | ******** UNSAT ************* |
| | |
| | 1)NOTE: PLANS ARE NOW IN FOR PLAN REVIEW |
| | THE ELECTRICAL CODE HAS NOW CHANGED TO |
| | THE 2002 NEC AS OF JULY 1ST, 2003. |
| | PLEASE ADJUST. |
| | |
| | 2)NOTE: PLEASE SEE 700.12E FOR CIRCUIT- |
| | -ING OF EM/EXT LTS. THIS WAS ON FIRST |
| | REVIEW NOTES. |
| | |
| | 3)NOTE: PLEASE CLARIFY LIGHTING IN MAIN |
| | SANCTUARY. NEW OR EXISTING? LS 101 |
| | |
| | 4 )NOTE: PLEASE SHOW LOAD CALCULATIONS, |
| | PLEASE SHOW PER |
| | 220.3,220.10,220.11,220.13 ETC. |
| | PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| | AT 125% PER 215.3,230.42 |
| | 12 MONTH LOAD IS SHOWN, HOWEVER, HOW |
| | CAN THIS BE ACURATE DUE TO ADDITION OF |
| | NEW ELECTRICAL AND/ PANEL/LOADS?? |
| | LOAD IS ALREADY SHOWN AT 196 A'S |
| | PLEASE DO LOAD CALCULATIONS PER ABOVE. |
| | |
| | 5)NOTE: PLEASE SEE AN EQUIPMENT GROUND- |
| | -ING CONDUCTOR IS SHOWN FROM FPL TO |
| | MAIN?? PLEASE SEE 250.6, 250.24 THIS IS |
| | PARALLELING THE NEUTRAL. |
| | PLEASE VERIFY. |
| | |
| | 6)NOTE: PLEASE SEE FAC 61G15-23.002 AND |
| | 61G1-16.004. PLEASE INCLUDE ALL INFORMAT |
| | -ION ON TITLE BLOCKS FOR ARCH/ ENG. |
| | THIS IS REQUIRED FOR ALL TRADES AND |
| | ALL SHEETS WEATHER OR NOT COMMENT IS |
| | MADE BY OTHER REVIEWER(S). |
| | PLEASE INCLUDE CERTIFICATE OF AUTHORIZ- |
| | ATION REQ'D PER FS 471.023, 481.221 |
| | |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |